Honeywell 51304537‑100 (51304537100)
May 28, 2026

Honeywell 51304537‑100 (51304537100)

Product Introduction Model: 51304537‑100 (Alias: 51304537100) Type: CNI I/O Board (Control Network Interface) Manufacturer: Honeywell Series: TDC3000 / TPS DCS Description: The 51304537‑100 is a CNI (Control Network Interface) I/O board for Honeywell TDC3000/TPS systems. It acts as an interface between the UCN (Universal Control Network) and local I/O modules, enabling data exchange and control signal routing for process control loops.

Description

Technical Specifications

  • Part Number: 51304537‑100 (51304537100)

  • Alternative ID: CNI I/O Board, PWB CNI I/O, Rev B

  • Module Type: Control Network Interface (CNI)

  • System Compatibility: Honeywell TDC3000 / TPS (UCN network)

  • Processor: On‑board 16‑bit microcontroller

  • Memory: 128 KB RAM, 256 KB Flash (firmware)

  • Network Interface: UCN (1 Mbps, redundant A/B, 75Ω coaxial)

  • I/O Interface: Backplane connector for IOPs (I/O Processor modules)

  • Power: 24 VDC ±10%, 400 mA (backplane)

  • Power Consumption: ~9.6 W

  • Operating Temperature: 0°C to +60°C

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 220 × 120 × 25 mm

  • Weight: ~0.33 kg

  • Coating: Standard (non‑conformal)

  • Certifications: CE, RoHS compliant

  • Revisions: Common Rev B (hardware/firmware)

  • Status: Discontinued (legacy replacement only)

Interface & Communication Configuration

  • Host Network: UCN (redundant A/B, 1 Mbps) – connects to system controllers (APM, HPM)

  • I/O Backplane: Direct interface to TDC3000 IOPs (analog/digital I/O cards)

  • Redundancy: Supports UCN A/B redundancy; module can be paired for fault tolerance

  • Diagnostics: On‑board LEDs for power, UCN link, and module health; remote fault reporting via UCN

  • Hot Swap: Yes (replace without system shutdown)

  • FTA Compatibility: N/A (direct backplane connection to IOPs)

Core Functions

  1. UCN‑to‑I/O Routing: Transfers process data and control signals between UCN and local I/O modules。

  2. I/O Data Acquisition: Collects analog/digital input data from field devices via IOPs.

  3. Control Signal Distribution: Sends regulatory/sequential control outputs from UCN controllers to field actuators.

  4. Network Communication Management: Manages UCN protocol, error checking, and data packet routing.

  5. Diagnostics & Status Reporting: Monitors module and I/O health; reports alarms to system HMI.

  6. Redundancy Switching: Supports automatic failover between redundant UCN paths.

Application Scenarios

  • TDC3000/TPS DCS: Core interface module connecting UCN to I/O subsystems。

  • Process Industries: Chemical, petrochemical, oil & gas, power, pulp & paper, pharmaceuticals。

  • Mixed I/O Environments: Systems requiring integration of analog, digital, and serial I/O.

  • Legacy System Maintenance: Replacement for aging CNI boards in TDC3000 migrations.

Compatibility Note

  • System Compatibility: Honeywell TDC3000/TPS (UCN network mandatory)

  • Replacement: 51304537‑100 (Standard) ↔ 51304537‑200 (Conformal Coated, Rev F)

  • Firmware: Requires TDC3000 firmware Rev 300+ for full CNI functionality

  • Key Difference: 51304537‑100 = Standard Coating; 51304537‑200 = Conformal Coating for harsh environments