Part Number: 51304516‑100 (51304516100)
Module Type: UCN Smart Transmitter Interface (STIM)
Network: UCN (Universal Control Network), 1 Mbps
Field Protocols: HART, Honeywell Smart Protocol
Channel Capacity: 16 smart transmitters (multidrop)
Signal Input: 4–20 mA analog + digital overlay (HART)
Power: 24 VDC ±10%, 150 mA (backplane)
Power Consumption: ~3.6 W
Operating Temperature: 0°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 220 × 120 × 30 mm
Weight: ~0.4 kg
Revisions: Common Rev A, B, C
Status: Discontinued (legacy replacement only)
Interface & Communication Configuration
Host Interface: UCN network (75Ω coaxial, redundant A/B)
Field Interface: 16 × 4–20 mA/HART channels (isolated)
Redundancy: Supports UCN A/B redundancy; field channels non‑redundant
Diagnostics: On‑board LEDs for UCN link, power, and channel status; remote alarm reporting
Wiring: Shielded twisted pair for field transmitters; 75Ω coax for UCN
Hot Swap: Yes (replace without system shutdown)
Core Functions
Smart Transmitter Integration: Connects HART/Honeywell smart transmitters to TDC3000 UCN.
Multidrop Communication: Up to 16 devices per card, reducing wiring and hardware cost.
Digital Configuration: Remote setup, calibration, and parameter adjustment of field transmitters.
Data Acquisition: Converts 4–20 mA analog signals to digital data for DCS processing.
Diagnostics & Alarms: Monitors transmitter health, detects faults (e.g., open circuit, overrange), and reports to DCS.
Protocol Conversion: Translates HART/smart protocol to UCN for seamless system integration.
Application Scenarios
TDC3000/TPS DCS: Primary interface for smart transmitters in process industries.
Process Plants: Chemical, petrochemical, power, pulp & paper, oil & gas.
Smart Field Device Networks: Environments with large numbers of HART‑enabled transmitters.
Legacy System Modernization: Upgrading analog‑only DCS to digital smart instrumentation.
Redundant Control Systems: Works with redundant UCN networks for high‑availability applications.
Compatibility Note
System Compatibility: Honeywell TDC3000/TPS (UCN network required)
Field Device Compatibility: HART 5/7, Honeywell Smart Transmitters (e.g., ST3000)
Replacement: Direct replacement for 51304516‑200 (UCN Smart MV Xmtr Interface)
Firmware: Requires TDC3000 firmware Rev 400+ for full HART support