Honeywell 51304493‑250 (51304493250)
Description
Technical Specifications
Part Number: 51304493‑250 (51304493250)
Module Type: APM/PM UCN Modem Card, Conformal Coated
Communication Rate: 1 Mbps (UCN network standard)
Transmission Medium: 75Ω coaxial cable (RG‑6/RG‑11); fiber via media converter
Network Topology: Peer‑to‑peer, redundant UCN (dual modem support)
Operating Voltage: 5 VDC ±5% (backplane‑powered)
Power Consumption: ~15 W
Operating Temperature: 0°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 233 × 120 × 25 mm (APM/PM slot form factor)
Weight: ~0.62–0.75 kg
Certifications: UL‑listed, CE‑compliant, CSA‑certified
Coating: Conformal coated (harsh/environmentally challenging areas)
Revisions: Common Rev E, H, N
Interface & Communication Configuration
Controller Interface: APM/PM backplane (TDC3000/TPS controller slot)
Network Interface: UCN (1 Mbps, connects to IOPs, FTA, and other UCN nodes)
Redundancy: Dual modem cards (primary/backup) for fault‑tolerant UCN
Diagnostics: On‑board LED status indicators; UCN link fault detection; controller bus diagnostics
Wiring: 75Ω coaxial cable for UCN trunk; shielded connectors recommended
Hot Swap: Yes (replace module without system shutdown)
Core Functions
UCN Communication Bridge: Connects APM/PM controller to all UCN IOPs (DI/DO/AI/AO) and field devices.
High‑Speed Data Transfer: 1 Mbps ensures real‑time control for up to 63 UCN nodes.
Conformal Coating Protection: Resists moisture, dust, chemicals in harsh environments.
Redundant Network Support: Enables dual UCN paths to eliminate single points of failure.
Signal Conditioning: Amplifies/conditions UCN signals for long‑distance transmission (up to 10 km with fiber).
Fault Monitoring: Detects UCN cable breaks, signal loss, or node failures; reports to system alarms.
Application Scenarios
TDC3000/TPS DCS: Core communication card for APM/PM controllers in process industries.
Harsh Environments: Offshore, wastewater, chemical plants (coated version mandatory).
Process Control: Chemical, petrochemical, power, pulp & paper (UCN backbone).
Legacy System Expansion: Replacement/upgrade for aging TDC3000 modems in tough conditions.
Redundant Control Systems: Critical loops requiring 100% uptime (ESD, turbine control).
Compatibility Note
System Compatibility: Honeywell TDC3000/TPS (APM/PM controller slots only).
Network Compatibility: UCN (Universal Control Network) 1 Mbps protocol.
Difference from 51304493‑200: ‑250 is conformal coated; ‑200 is non‑coated (standard environment).
Replacement: Direct replacement for 51304493‑000/100/200 series modems (check revision compatibility).