Honeywell 51304493-200 (51304493200)
Description
Technical Specifications
Part Number: 51304493-200 (51304493200)
Module Type: APM/PM Modem Card (UCN Interface)
Communication Rate: 1 Mbps (UCN network standard)
Transmission Medium: Coaxial cable or fiber optic (via media converter)
Network Topology: Peer‑to‑peer, redundant UCN (dual modem support)
Operating Voltage: 5 VDC ±5% (backplane‑powered)
Power Consumption: ~15 W
Operating Temperature: 0°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 233 × 120 × 25 mm (APM slot form factor)
Weight: ~0.62 kg
Certifications: UL‑listed, CE‑compliant, CSA‑certified
Coating: Non‑conformal coated (standard)
Revisions: Common Rev K, N, E
Interface & Communication Configuration
Controller Interface: APM/PM backplane (TDC3000/TPS controller slot)
Network Interface: UCN (1 Mbps, connects to IOPs, FTA, and other nodes)
Redundancy: Dual modem cards (primary/backup) for fault‑tolerant UCN
Diagnostics: On‑board LED status indicators; UCN link fault detection; controller bus diagnostics
Wiring: 75Ω coaxial cable (RG‑6 or RG‑11) for UCN trunk
Hot Swap: Yes (replace without system shutdown)
Core Functions
UCN Communication Bridge: Connects APM/PM controller to all UCN IOPs (DI/DO/AI/AO) and field devices.
High‑Speed Data Transfer: 1 Mbps ensures real‑time control and data acquisition for up to 63 UCN nodes.
Redundant Network Support: Enables dual UCN paths to eliminate single points of failure.
Signal Conditioning: Amplifies/conditions UCN signals for long‑distance transmission (up to 10 km with fiber).
Fault Monitoring: Detects UCN cable breaks, signal loss, or node failures; reports to system alarms.
Backplane Integration: Draws power and control signals directly from the APM/PM backplane.
Application Scenarios
TDC3000/TPS DCS: Core communication card for APM/PM controllers in process industries.
Process Control: Chemical, petrochemical, power, pulp & paper (UCN network backbone).
Legacy System Expansion: Replacement/upgrade for aging TDC3000 modems in operational plants.
Redundant Control Systems: Critical loops requiring 100% uptime (e.g., ESD, turbine control).
Remote I/O Connectivity: Links controllers to distributed IOPs across large plant areas.
Compatibility Note
System Compatibility: Honeywell TDC3000/TPS (APM/PM controller slots only).
Network Compatibility: UCN (Universal Control Network) 1 Mbps protocol.
Replacement: Direct replacement for 51304493‑000/100 series modems (check revision compatibility).
Get a Quote