Honeywell 51304485-150 (51304485150, MU-PDIX02)
Description
Technical Specifications
Part Number: 51304485-150 (51304485150)
Module Type: MU‑PDIX02, Digital Input IOP (DI), Conformal Coated
Channel Configuration: 32 × isolated digital input channels (4 banks of 8)
Input Signal Types: Dry contact (NO/NC), 24 VDC logic (sink/source selectable)
Input Voltage: Logic high ≥20 VDC; logic low ≤10 VDC
Sense Current: ON ≥4.5 mA; OFF ≤2.8 mA
Isolation: Channel‑to‑backplane 1500 VAC rms; bank‑to‑bank isolation
Response Time: ≤10 ms per channel
Power Supply: 24 VDC ±10%, 0.5 A (UCN backplane‑powered)
Operating Temperature: 0°C to +60°C
Storage Temperature: ‑40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 130 × 35 × 110 mm (UCN IOP form factor)
Weight: ~0.65 kg
Certifications: UL‑listed, CE‑compliant, CSA‑certified
Connectors: UCN 96‑pin edge connector; 50‑pin ribbon cable to FTA
Status Indicators: Power LED, fault LED, 32 channel status LEDs
Coating: Conformal coated (harsh/environmentally challenging areas)
Interface & Communication Configuration
DCS Interface: UCN backplane (1 Mbps, TDC3000/TPS/Experion PKS compatible)
FTA Interface: 50‑pin ribbon cable to 51304484‑150 (conformal coated DI FTA)
Diagnostics: On‑board self‑diagnostics; per‑channel open/short detection; FTA fault monitoring
Wiring: Shielded twisted pair (STP) recommended for 24 VDC signals
Redundancy: Supported (dual IOPs hot standby, shared FTA)
Hot Swap: Yes (replace module without system shutdown)
Core Functions
32‑Channel Digital Input: High‑density discrete input monitoring for field devices.
Conformal Coating: Protects against moisture, dust, chemicals in harsh environments.
Isolated Banks: 1500 VAC isolation prevents field noise/transients from damaging system.
Dry Contact/24 VDC Compatibility: Works with mechanical relays and solid‑state outputs.
Fast Response: ≤10 ms ensures real‑time status for critical interlocks.
Redundancy Support: Hot‑standby for high‑availability applications (safety systems).
Backplane‑Powered: No external PSU needed; draws power from UCN backplane.
Application Scenarios
Process Industries: Chemical, petrochemical, power, pulp & paper (equipment status, safety interlocks).
Harsh Environments: Offshore, wastewater, high‑humidity/chemical areas (coated version preferred).
Field Device Monitoring: Limit/pressure/level switches, relay contacts, motor run/stop status.
Legacy DCS: Replacement/expansion for TDC3000/TPS needing 32‑channel DI in tough conditions.
Safety & Alarms: Critical interlocks, E‑stop circuits, alarm annunciation.
Compatibility Note
System Compatibility: Honeywell TDC3000/TPS and Experion PKS (UCN).
FTA Compatibility: 51304484‑150 (conformal coated DI FTA).
Difference from 51304485‑100: ‑150 is conformal coated; ‑100 is non‑coated (standard environment).
Get a Quote