Honeywell 51304477-150 (51304477150)
May 28, 2026

Honeywell 51304477-150 (51304477150)

Model: 51304477-150 (Alias: 51304477150) Type: Low-Level Analog Input Multiplexer FTA (RTD Compact Termination Module) Manufacturer: Honeywell Series: TDC3000 / TPS UCN DCS Description: The 51304477-150 is a 16‑channel compact low‑level analog input FTA dedicated to RTD (PT100/PT1000) signals for Honeywell TDC3000/TPS UCN DCS. It provides precision multiplexing and signal conditioning in a reduced form factor for space‑constrained cabinets。

Description

Technical Specifications

  • Part Number: 51304477-150 (51304477150)

  • Module Type: Compact RTD Analog Input FTA (LLAI MUX RTD)

  • Channel Configuration: 16 × single‑ended RTD input channels

  • Signal Types: Platinum RTD (PT100, PT1000), low‑level voltage (mV)

  • Input Range: PT100: -200°C to +850°C; 0–100 mV

  • Isolation: Channel‑to‑backplane 500 VAC rms basic isolation; non‑isolated between channels

  • Resolution: 16‑bit per channel

  • Accuracy: ±0.05% FS (full scale) at 25°C

  • Power Supply: 24 VDC ±10%, 0.35 A (backplane‑powered)

  • Operating Temperature: -20°C to +60°C

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 100 × 60 × 110 mm (Compact Size)

  • Weight: ~0.28 kg

  • Certifications: UL‑listed, CE‑compliant

  • Terminals: Screw‑type (14–24 AWG, 3‑wire RTD wiring)

  • Connectors: UCN 96‑pin edge connector (backplane)

  • Status Indicators: Power LED, fault LED

Interface & Communication Configuration

  • DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)

  • Field Interface: 16‑channel screw terminals (PT100/PT1000 RTD sensors)

  • Diagnostics: On‑board self‑diagnostics; per‑channel open/short circuit detection

  • Wiring: Accepts 14–24 AWG stranded copper wire (3‑wire RTD recommended)

  • Redundancy: Not supported (non‑redundant FTA)

Core Functions

  1. 16‑Channel RTD Input: Precision multiplexing for PT100/PT1000 temperature sensors.

  2. Low‑Level Signal Conditioning: Amplification, filtering, and cold‑junction compensation for RTDs.

  3. Basic Isolation: 500 VAC channel‑to‑backplane isolation protects DCS from field faults.

  4. High Accuracy & Resolution: 16‑bit resolution with ±0.05% FS accuracy for precise temperature measurement.

  5. Compact & Lightweight: 10×6×11 cm, 0.28 kg; saves cabinet space vs. standard Size B FTA。

  6. Backplane‑Powered: Eliminates external power supplies.

Application Scenarios

  • Process Industries: Chemical, petrochemical, power generation, pulp & paper (precision temperature monitoring).

  • Temperature Measurement: PT100/PT1000 RTDs for reactors, furnaces, pipelines, storage tanks.

  • Legacy DCS Systems: Replacement/expansion for TDC3000/TPS needing compact 16‑channel RTD FTA.

  • Space‑Constrained Cabinets: Ideal for compact or densely populated I/O cabinets.

Compatibility Note

  • Form‑factor: Compact UCN FTA (smaller than 51304477‑100 Size B).

  • System Compatibility: Honeywell TDC3000/TPS and Experion PKS (via UCN AI IOP).

  • Key Difference from 51304477‑100: 51304477‑150 is ultra‑compact (100×60×110 mm, 0.28 kg); 51304477‑100 is Size B (135×85×55 mm, 0.75 kg)。