Honeywell 51304477-100 (51304477100, MU-TAMR02)
Description
Technical Specifications
Part Number: 51304477-100 (51304477100)
Module Type: MU‑TAMR02, RTD Analog Input FTA
Channel Configuration: 16 × single‑ended RTD input channels
Signal Types: Platinum RTD (PT100, PT1000), low‑level voltage
Input Range: PT100: -200°C to +850°C; 0–100 mV
Isolation: Channel‑to‑backplane 500 VAC rms basic isolation; non‑isolated between channels
Resolution: 16‑bit per channel
Accuracy: ±0.05% FS (full scale) at 25°C
Power Supply: 24 VDC ±10%, 0.4 A (backplane‑powered)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 135 × 85 × 55 mm (Size B UCN form factor)
Weight: ~0.75 kg
Certifications: UL‑listed, CE‑compliant
Terminals: Compression‑type (14–24 AWG, RTD field wiring)
Connectors: UCN 96‑pin edge connector (backplane)
Status Indicators: Power LED, fault LED, channel activity LEDs
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)
Field Interface: 16‑channel compression terminals (RTD sensors)
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN; open/short circuit detection per channel
Wiring: Accepts 14–24 AWG stranded copper wire (3‑wire RTD recommended)
Redundancy: Not supported (non‑redundant FTA)
Core Functions
16‑Channel RTD Input: Precision multiplexing for PT100/PT1000 temperature sensors.
Low‑Level Signal Conditioning: Amplification, filtering, and cold‑junction compensation for RTDs.
Basic Isolation: 500 VAC channel‑to‑backplane isolation protects DCS from field faults.
High Accuracy & Resolution: 16‑bit resolution with ±0.05% FS accuracy for precise temperature control.
Backplane‑Powered: Eliminates external power supplies; draws power from UCN backplane.
Fault Detection: Per‑channel open/short circuit monitoring for RTD sensor diagnostics.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (precision temperature monitoring).
Temperature Measurement: PT100/PT1000 RTD sensors for reactors, furnaces, pipelines, and storage tanks.
Legacy DCS Systems: Replacement/expansion for TDC3000/TPS needing 16‑channel RTD input FTA.
Size B UCN Cabinets: Standard UCN form factor for compatibility with existing I/O cabinet layouts.
Compatibility Note
Form‑factor compatible with Size B UCN FTAs.
Functionally compatible with Honeywell TDC3000/TPS and Experion PKS (via UCN AI IOP).
Key Difference from 51304453/76 Series: 51304477‑100 is RTD‑specific low‑level input FTA; others are analog input/output for standard 4–20 mA/1–5 V signals.
Get a Quote