Honeywell 51304453-150 (51304453150, MC-TAIH02)
Description
Technical Specifications
Part Number: 51304453-150 (51304453150)
Module Type: MC‑TAIH02, HLAI FTA (High‑Level Analog Input)
Channel Configuration: 16 × single‑ended analog input channels
Signal Types: 4–20 mA (current), 1–5 VDC, 0–10 VDC, ±5 VDC
Input Impedance: ≥1 MΩ (voltage), 250 Ω (current, internal shunt)
Isolation: Channel‑to‑backplane 500 VAC rms basic isolation; non‑isolated between channels
Resolution: 16‑bit per channel
Accuracy: ±0.1% FS (full scale) at 25°C
Power Supply: 24 VDC ±10%, 0.3 A (backplane‑powered)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)
Weight: ~2.0 kg
Certifications: UL‑listed, CE‑compliant
Terminals: Screw‑type (14–24 AWG, field wiring)
Connectors: UCN 96‑pin edge connector (backplane), STI interface
Status Indicators: Power LED, fault LED
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS & Experion PKS compatible)
Field Interface: 16‑channel screw terminals (4–20 mA / 1–5 VDC devices)
STI Interface: Smart Transmitter Interface for intelligent field device communication
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN
Wiring: Accepts 14–24 AWG stranded copper wire
Redundancy: Supports redundant HLAI IOP (Input/Output Processor)
Core Functions
16‑Channel High‑Level Analog Input: Acquires 4–20 mA/1–5 VDC signals from pressure, temperature, flow transmitters.
Signal Conditioning: Built‑in 250 Ω shunts for current‑to‑voltage conversion; EMI/RFI filtering.
STI Support: Enables communication with smart transmitters for enhanced diagnostics and data.
Basic Isolation: 500 VAC channel‑to‑backplane isolation protects DCS from field noise and ground loops.
High Accuracy & Resolution: 16‑bit resolution with ±0.1% FS accuracy for precise process monitoring.
Backplane‑Powered: Eliminates external power supplies; draws power from UCN backplane.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (analog sensor monitoring).
High‑Level Signal Acquisition: Transmitters (4–20 mA), voltage‑based sensors, process indicators.
Legacy DCS Systems: Replacement/expansion for TDC3000/TPS and Experion PKS needing 16‑channel HLAI with STI.
Smart Device Integration: Plants using Honeywell STI for intelligent transmitter communication.
Compatibility Note
Form‑factor compatible with Size C UCN FTAs (e.g., 51304446 DO series, 51304451 DO Standby).
Functionally compatible with Honeywell TDC3000/TPS and Experion PKS (via UCN IOP).
Key Difference from 51304453‑100: 51304453‑150 (MC‑TAIH02) adds STI support for smart transmitters; 51304453‑100 (MU‑TAIH02) is standard HLAI without STI.