Honeywell 51304453-100 (51304453100, MU-TAIH02)
May 28, 2026

Honeywell 51304453-100 (51304453100, MU-TAIH02)

Product Introduction Model: 51304453-100 (Alias: 51304453100, MU‑TAIH02) Type: High‑Level Analog Input (HLAI) FTA with STI (System Termination Interface) Manufacturer: Honeywell Series: TDC3000 / TPS UCN DCS Description: The 51304453-100 (MU‑TAIH02) is a 16‑channel high‑level analog input field termination assembly (FTA) designed for Honeywell TDC3000/TPS UCN DCS systems. It accepts 1–5 VDC, 4–20 mA and other high‑level analog signals from transmitters and field sensors, providing robust signal conditioning and termination via a System Termination Interface (STI).

Description

Technical Specifications

  • Part Number: 51304453-100 (51304453100)

  • Module Type: MU‑TAIH02, HLAI FTA (High‑Level Analog Input)

  • Channel Configuration: 16 × single‑ended analog input channels

  • Signal Types: 4–20 mA (current), 1–5 VDC (voltage), 0–10 VDC, ±5 VDC

  • Input Impedance: ≥1 MΩ (voltage), 250 Ω (current, internal shunt)

  • Isolation: Channel‑to‑backplane 500 VAC rms basic isolation; non‑isolated between channels

  • Resolution: 16‑bit per channel

  • Accuracy: ±0.1% FS (full scale) at 25°C

  • Power Supply: 24 VDC ±10%, 0.3 A (backplane‑powered)

  • Operating Temperature: -20°C to +60°C

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)

  • Weight: ~1.5 kg

  • Certifications: UL‑listed, CE‑compliant

  • Terminals: Screw‑type (14–24 AWG, field wiring)

  • Connectors: UCN 96‑pin edge connector (backplane), STI interface

  • Status Indicators: Power LED, fault LED

Interface & Communication Configuration

  • DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)

  • Field Interface: 16‑channel screw terminals (4–20 mA / 1–5 VDC devices)

  • STI Interface: System Termination Interface for centralized marshalling

  • Diagnostics: On‑board self‑diagnostics with fault reporting via UCN

  • Wiring: Accepts 14–24 AWG stranded copper wire

  • Redundancy: Supports redundant HLAI IOP (Input/Output Processor)

Core Functions

  1. 16‑Channel High‑Level Analog Input: Acquires 4–20 mA/1–5 VDC signals from transmitters, pressure/temperature/flow sensors.

  2. Signal Conditioning: Built‑in 250 Ω shunts for current‑to‑voltage conversion; EMI/RFI filtering.

  3. STI‑Enabled Marshalling: Integrates with System Termination Interface for simplified, centralized field wiring.

  4. Basic Isolation: 500 VAC channel‑to‑backplane isolation protects DCS from field noise and ground loops.

  5. High Accuracy & Resolution: 16‑bit resolution with ±0.1% FS accuracy for precise process monitoring.

  6. Backplane‑Powered: Eliminates external power supplies; draws power from UCN backplane.

Application Scenarios

  • Process Industries: Chemical, petrochemical, power generation, pulp & paper (analog sensor monitoring).

  • High‑Level Signal Acquisition: Transmitters (4–20 mA), voltage‑based sensors, and process indicators.

  • Legacy DCS Systems: Replacement/expansion for TDC3000/TPS needing 16‑channel HLAI with STI.

  • Centralized Marshalling: Plants using Honeywell STI for organized, scalable field wiring.

Compatibility Note

  • Form‑factor compatible with Size C UCN FTAs (e.g., 51304446 DO series, 51304451 DO Standby).

  • Functionally compatible with Honeywell TDC3000/TPS and Experion PKS (via UCN IOP).

  • Key Difference: Optimized for high‑level analog inputs (4–20 mA/1–5 VDC) with STI support, unlike digital FTAs.


Get a Quote