Description
Technical Specifications
Part Number: 51304451-100 (51304451100)
Module Type: Digital Output (DO) Standby Manual FTA
Channel Configuration: 16 × digital output channels (with manual/auto switch)
Load Voltage Rating: 24 VDC (nominal, 18–30 VDC range)
Contact Rating: 0.5 A per channel (resistive load)
Isolation: Channel‑to‑backplane 500 VAC rms basic isolation
Switchover: Manual/auto toggle per channel (local override capability)
Power Supply: 24 VDC ±10% (backplane‑powered)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)
Weight: ~2.5 kg
Certifications: UL‑listed, CE‑compliant
Terminals: Screw‑type (14–24 AWG)
Status Indicators: Power LED, channel status LEDs, manual mode indicator
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)
Field Interface: Screw terminals (16 channels for 24 VDC loads)
Switchover Control: Local manual/auto switch per channel
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN
Wiring: Accepts 14–24 AWG stranded copper wire
Connector: UCN 96‑pin edge connector (gold‑plated contacts)
Core Functions
16‑Channel Digital Output Control: Drives 24 VDC field devices (solenoids, relays, indicators) in TDC3000/TPS systems.
Manual/Auto Switchover: Each channel has a local toggle switch for manual override (bypass DCS control) or auto mode (DCS‑controlled).
Standby Operation: Enables safe maintenance or backup control of critical outputs without DCS intervention.
Basic Isolation: 500 VAC channel‑to‑backplane isolation protects DCS from field noise.
Status Monitoring: LEDs for power, channel status, and manual mode provide quick visual diagnostics.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation (critical valve/actuator control).
Critical Device Control: Solenoid valves, emergency shutdown (ESD) relays, and safety indicators requiring local override.
Legacy DCS Systems: Replacement/expansion for TDC3000/TPS needing manual standby DO capability.
Maintenance & Backup: Applications where local manual control is required during DCS downtime or maintenance.
Compatibility Note
Form‑factor compatible with Size C UCN FTAs (e.g., 51304446 series).
Functionally compatible with Honeywell TDC3000/TPS and Experion PKS systems.
Key Difference: Unlike standard DO FTAs (e.g., 51304446 series), this model adds per‑channel manual/auto switchover for standby operation.