Honeywell 51304446-150 (MU-TDON12)
Description
Technical Specifications
Part Number: 51304446-150 (51304446150)
Module Type: MU-TDON12 (Digital Output FTA, Non‑Isolated)
Channel Configuration: 12 × independent solid‑state digital outputs (non‑isolated)
Load Voltage Rating: 24 VDC (nominal, 18–30 VDC range)
Contact Rating: 0.5 A per channel (resistive load), 1 A max per module
Isolation: None (non‑isolated design; channel‑to‑backplane 500 VAC rms basic isolation)
Response Time: ≤1 ms per channel
Power Supply: 24 VDC ±10%, 0.2 A (backplane‑powered)
Operating Temperature: -20°C to +60°C (general/moderate environment)
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)
Weight: ~2.6 kg
Certifications: CE‑compliant, UL‑listed (no RoHS)
Coating: Standard conformal coating (improved dust/moisture/corrosion resistance vs -100)
Terminals: Screw‑type (14–24 AWG, standard vibration tolerance)
Status Indicators: Power/Fault LED, individual channel status LEDs
Current Draw: ≤2.4 W
Vibration Resistance: 2g, 10–500 Hz (general industrial tolerance)
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS/Experion PKS compatible)
Field Interface: Screw terminals (12 channels for 24 VDC loads, non‑isolated)
Redundancy: Supports redundant IOP (Input/Output Processor) configurations
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN; LED status for quick troubleshooting
Wiring: Accepts 14–24 AWG stranded copper wire
Connector: UCN 96‑pin edge connector (gold‑plated contacts)
Core Functions
12‑Channel Digital Output Switching: Controls 24 VDC field devices (solenoids, relay coils, indicators, small actuators) via solid‑state circuits.
Basic Electrical Isolation: 500 VAC channel‑to‑backplane isolation protects DCS from load‑side noise (non‑isolated between channels).
Moderate Environment Protection: Standard conformal coating improves resistance to dust, moisture, and mild corrosives vs basic coating.
CE/UL Compliance: Meets European and North American safety standards for wider industrial deployments.
Backplane‑Powered: Draws power from UCN backplane, eliminating external power supplies.
Status Monitoring: Individual channel LEDs enable quick visual status checks for maintenance.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (general/moderate non‑corrosive environments).
Low‑Voltage Device Control: 24 VDC solenoid valves, relay coils, LED indicators, and small‑scale actuators.
Legacy DCS Systems: Replacement/expansion for Honeywell TDC3000/TPS needing CE/UL compliance.
Indoor/Protected Zones: Control rooms, dry manufacturing floors, and low‑humidity facilities.
Global Deployments: Projects requiring CE marking for European market access.
51304446 Series Key Differences
| Feature | 51304446-100 | 51304446-150 | 51304446-200 |
|---|---|---|---|
| Revision | 100 | 150 | 200 |
| Isolation | Non‑Isolated | Non‑Isolated | Non‑Isolated |
| Conformal Coating | Basic | Standard | Enhanced |
| CE Certified | ❌ No | ✅ Yes | ✅ Yes |
| UL Certified | ✅ Yes | ✅ Yes | ✅ Yes |
| RoHS Compliant | ❌ No | ❌ No | ✅ Yes |
| Operating Temp | -20°C~+60°C | -20°C~+60°C | -20°C~+70°C |
| Environment | General (UL only) | Moderate (CE/UL) | Harsh (CE/UL/RoHS) |
Compatibility Note
Form‑factor compatible with other 51304446 series (Size C, UCN connector).
Functionally compatible with 51304441 series (digital output, UCN protocol).
Recommended for legacy TDC3000/TPS systems needing 24 VDC non‑isolated digital outputs in moderate environments with CE/UL compliance.
Get a Quote