Honeywell 51304446-100 (MU-TDON12)
May 28, 2026

Honeywell 51304446-100 (MU-TDON12)

Product Introduction Model: 51304446-100 (Alias: 51304446100, MU-TDON12) Type: 12‑Channel Digital Output FTA (Field Termination Assembly) Manufacturer: Honeywell Series: TDC3000 / TPS UCN DCS, MU Series I/O Description: The 51304446-100 (MU-TDON12) is a 24 VDC, 12‑channel digital output FTA with screw terminals, basic conformal coating, UL compliance, designed for general industrial environments in Honeywell TDC3000/TPS and Experion PKS systems. It provides solid‑state switching for low‑voltage field devices, acting as the interface between DCS control logic and 24 VDC loads.

Description

Technical Specifications

  • Part Number: 51304446-100 (51304446100)

  • Module Type: MU-TDON12 (Digital Output FTA)

  • Channel Configuration: 12 × independent solid‑state digital outputs

  • Load Voltage Rating: 24 VDC (nominal, 18–30 VDC range)

  • Contact Rating: 0.5 A per channel (resistive load), 1 A max per module

  • Isolation: 500 VAC rms (channel‑to‑backplane)

  • Response Time: ≤1 ms per channel

  • Power Supply: 24 VDC ±10%, 0.2 A (backplane‑powered)

  • Operating Temperature: -20°C to +60°C (general environment)

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)

  • Weight: ~2.6 kg

  • Certifications: UL‑listed (no CE/RoHS)

  • Coating: Basic conformal coating (dust/moisture resistance)

  • Terminals: Screw‑type (14–24 AWG, standard vibration tolerance)

  • Status Indicators: Power/Fault LED, individual channel status LEDs

  • Current Draw: ≤2.4 W

  • Vibration Resistance: 2g, 10–500 Hz (general industrial tolerance)

Interface & Communication Configuration

  • DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS/Experion PKS compatible)

  • Field Interface: Screw terminals (12 channels for 24 VDC loads)

  • Redundancy: Supports redundant IOP (Input/Output Processor) configurations

  • Diagnostics: On‑board self‑diagnostics with fault reporting via UCN; LED status for quick troubleshooting

  • Wiring: Accepts 14–24 AWG stranded copper wire

  • Connector: UCN 96‑pin edge connector (gold‑plated contacts)

Core Functions

  1. 12‑Channel Digital Output Switching: Controls 24 VDC field devices (solenoids, relays, indicators, small actuators) via solid‑state circuits.

  2. Low‑Voltage Isolation: 500 VAC isolation protects DCS from load‑side electrical noise.

  3. General Environment Protection: Basic conformal coating safeguards against dust and moisture in non‑harsh areas.

  4. UL Compliance: Meets UL safety standards for industrial deployments.

  5. Backplane‑Powered: Draws power from UCN backplane, eliminating external power supplies.

  6. Status Monitoring: Individual channel LEDs enable quick visual status checks.

Application Scenarios

  • Process Industries: General chemical, petrochemical, power generation, pulp & paper facilities (non‑harsh/non‑corrosive environments).

  • Low‑Voltage Device Control: 24 VDC solenoid valves, relay coils, LED indicators, and small‑scale actuators.

  • Legacy DCS Systems: Replacement/expansion for Honeywell TDC3000/TPS installations in general plant areas.

  • Non‑Corrosive Zones: Indoor control rooms, dry manufacturing floors, and low‑humidity facilities.

  • Cost‑Sensitive Deployments: Projects requiring UL compliance without CE/RoHS mandates.

Compatibility Note

  • Form‑factor compatible with other 51304446 series (Size C, UCN connector).

  • Functionally compatible with 51304441 series (digital output, UCN protocol).

  • Recommended for legacy TDC3000/TPS systems needing 24 VDC digital outputs in general environments with UL compliance.