Honeywell 51304443-200 (MU-TDOR52)
Description
Technical Specifications
Part Number: 51304443-200 (51304443200)
Module Type: MU-TDOR52 (Relay Output FTA)
Channel Configuration: 16 × independent electromechanical relay outputs (dry contact)
Load Voltage Rating: 120 VAC / 125 VDC (max)
Contact Rating: 6 A per channel (resistive load), 1/3 HP at 120 VAC
Isolation: 1500 VAC rms (channel‑to‑backplane)
Response Time: ≤10 ms per channel
Power Supply: 24 VDC ±10%, 0.3 A (backplane‑powered)
Operating Temperature: -20°C to +70°C (harsh environment)
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)
Weight: ~2.5 kg
Certifications: CE‑compliant, UL‑listed, RoHS‑compliant
Coating: Enhanced conformal coating (harsh environment protection)
Terminals: Heavy‑duty screw‑type (12–22 AWG, vibration‑resistant)
Status Indicators: Power/Fault LED, individual channel status LEDs
Current Draw: ≤3.6 W
Vibration Resistance: 5g, 10–500 Hz (harsh industrial tolerance)
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS/Experion PKS compatible)
Field Interface: Heavy‑duty screw terminals (16 channels for 120 VAC/125 VDC loads)
Redundancy: Supports redundant IOP (Input/Output Processor) configurations
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN; LED status for quick troubleshooting
Wiring: Accepts 12–22 AWG stranded copper wire
Connector: UCN 96‑pin edge connector (gold‑plated contacts)
Core Functions
16‑Channel Relay Output Switching: Controls high‑power field devices (motor starters, solenoids, alarms, actuators) via dry‑contact relays.
High‑Voltage Isolation: 1500 VAC isolation protects DCS from load‑side electrical noise and voltage spikes.
Harsh Environment Protection: Enhanced conformal coating safeguards against dust, moisture, and corrosive gases in harsh areas.
CE/UL/RoHS Compliance: Meets global safety and environmental standards for industrial deployments.
Backplane‑Powered: Draws power from UCN backplane, eliminating external power supplies.
Status Monitoring: Individual channel LEDs enable quick visual status checks.
Vibration Resistance: Heavy‑duty screw terminals and 5g vibration rating ensure reliability in high‑vibration environments.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper facilities (harsh/corrosive environments).
High‑Power Device Control: 120 VAC/125 VDC motor starters, solenoid valves, alarm beacons, and heavy‑duty actuators.
Legacy DCS Systems: Replacement/expansion for Honeywell TDC3000/TPS installations in harsh plant areas.
Corrosive/High‑Vibration Zones: Outdoor control rooms, manufacturing floors with heavy machinery, and high‑humidity facilities.
Global Deployments: Facilities requiring CE, UL, and RoHS markings for compliance.
Key Differences: 51304443 Series Variants
| Feature | 51304443-100 | 51304443-150 | 51304443-200 |
|---|---|---|---|
| Revision | 100 | 150 | 200 |
| Series | MU-TDOR12 | MU-TDOR12 | MU-TDOR52 |
| Input Voltage | 120 VAC/125 VDC | 120 VAC/125 VDC | 120 VAC/125 VDC |
| Conformal Coating | Basic | Standard | Enhanced |
| CE Certified | ❌ No | ✅ Yes | ✅ Yes |
| UL Certified | ✅ Yes | ✅ Yes | ✅ Yes |
| RoHS Compliant | ❌ No | ❌ No | ✅ Yes |
| Terminals | Compression | Compression | Heavy‑Duty Screw |
| Operating Temp | -20°C~+60°C | -20°C~+60°C | -20°C~+70°C |
| Vibration Resistance | 2g | 2g | 5g |
| Environment | Standard | General (CE/UL) | Extreme Harsh (CE/UL/RoHS) |
Compatibility Note
Form‑factor compatible with other 51304443 series (Size C, UCN connector).
Functionally compatible with 51309148 series (16‑channel relay output, UCN protocol).
Recommended for legacy TDC3000/TPS systems needing 120 VAC/125 VDC relay outputs in harsh environments with CE/UL/RoHS compliance.