Description
Product Introduction
Technical Specifications
Part Number: 51304441-225 (51304441225)
Module Type: MC-TDID52 (Digital Input FTA)
Channel Configuration: 32 × galvanically isolated digital input channels
Input Voltage: 24 VDC ±10% (dry contact or wet DC voltage)
Isolation: 1500 VAC rms (channel‑to‑backplane)
Response Time: ≤5 ms per channel (supports SOE recording)
Power Supply: 24 VDC ±10%, 0.5 A (backplane‑powered)
Operating Temperature: -40°C to +70°C (extended extreme harsh rating)
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing (corrosion‑resistant coating)
Dimensions (H×W×D): 270 × 185 × 95 mm (Size C, 18‑inch form factor)
Weight: ~2.6 kg (reinforced housing)
Certifications: CE‑compliant, UL‑listed, RoHS‑compliant
Coating: Enhanced conformal coating (extreme harsh environment protection)
Terminals: Heavy‑duty screw‑type (12–22 AWG, vibration‑resistant)
Status Indicators: Power/Fault LED, individual channel status LEDs
Current Draw: ≤4.0 W
Vibration Resistance: 5g, 10–500 Hz (industrial vibration tolerance)
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS/Experion PKS compatible)
Field Interface: Heavy‑duty screw terminals (32 channels for 24 VDC inputs)
Redundancy: Supports redundant IOP (Input/Output Processor) configurations
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN; LED status for quick troubleshooting
Wiring: Accepts 12–22 AWG stranded copper wire (heavy‑gauge compatibility)
Connector: UCN 96‑pin edge connector (gold‑plated contacts for reliability)
Core Functions
24 VDC Digital Input Monitoring: Captures low‑voltage discrete signals from switches, relays, and sensors (32‑channel high density for extreme environments).
Galvanic Isolation: 1500 VAC isolation protects DCS from electrical noise, ground loops, and voltage spikes in harsh plants.
Fast Response: 5 ms response time enables accurate sequence‑of‑events (SOE) logging for critical process troubleshooting.
Enhanced Conformal Coating: Protects against moisture, dust, corrosive gases, and chemical vapors (ideal for chemical/petrochemical zones).
CE/UL/RoHS Compliance: Meets global safety and environmental standards for international deployments.
Heavy‑Duty Termination: Vibration‑resistant screw terminals for high‑vibration areas (e.g., power plants, heavy machinery zones).
Extended Temperature Range: Operates reliably at up to +70°C and down to -40°C for extreme industrial environments.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (extreme harsh environments requiring CE/UL/RoHS).
Harsh Environment Monitoring: Outdoor installations, high‑humidity areas, corrosive industrial zones, and high‑vibration facilities.
Low‑Voltage Device Monitoring: 24 VDC limit switches, proximity sensors, relay contacts, and panel status lights in extreme conditions.
Legacy DCS Systems: Replacement/expansion for Honeywell TDC3000/TPS installations in harsh plant areas.
Global Deployments: Facilities requiring CE, UL, and RoHS markings for compliance.
Extreme Temperature Zones: Industrial areas with ambient temperatures ranging from -40°C to +70°C.
Key Differences: 51304441 Series Variants
| Feature | 51304441-100 | 51304441-125 | 51304441-175 | 51304441-200 | 51304441-225 |
|---|---|---|---|---|---|
| Revision | 100 | 125 | 175 | 200 | 225 |
| Series | MU-TDID12 | MU-TDID12 | MC-TDID12 | MU-TDID52 | MC-TDID52 |
| Input Voltage | 24 VDC | 24 VDC | 24 VDC | 24 VDC | 24 VDC |
| Conformal Coating | ❌ No | ❌ No | ✅ Standard | ✅ Enhanced | ✅ Enhanced+ |
| CE Certified | ❌ No | ✅ Yes | ✅ Yes | ✅ Yes | ✅ Yes |
| UL Certified | ❌ No | ❌ No | ✅ Yes | ✅ Yes | ✅ Yes |
| RoHS Compliant | ❌ No | ❌ No | ❌ No | ✅ Yes | ✅ Yes |
| Terminals | Compression | Compression | Compression | Heavy‑Duty Compression | Heavy‑Duty Screw |
| Operating Temp | -20°C~+60°C | -20°C~+60°C | -20°C~+60°C | -20°C~+70°C | -40°C~+70°C |
| Environment | Standard | Standard (CE) | Harsh (CE/UL) | Extreme Harsh (CE/UL/RoHS) | Ultra Extreme Harsh (CE/UL/RoHS) |
Compatibility Note
Form‑factor compatible with other 51304441 series (Size C, UCN connector).
Functionally compatible with 51304439 series (32‑channel isolated input, UCN protocol, different voltage).
Recommended for legacy TDC3000/TPS systems needing 24 VDC inputs in ultra‑extreme harsh environments with CE/UL/RoHS compliance.
Get a Quote