3IF792.9 Interface Module (B&R)
Description
3IF792.9 Interface Module (B&R)
Product Introduction
3IF792.9 is an aPCI multi-interface communication module from the B&R 2005 system platform. It integrates 2 X2X Link master stations and 1 RS232, specifically designed for the aPCI slot of B&R controllers. It can manage two sets of distributed I/O or servo drives simultaneously and provides serial port connections for third-party devices, suitable for complex automation systems that require multi-bus isolation networking and serial communication. It is the core module of the compact multi-interface expansion.
Basic Information
Product Model: 3IF792.9
Brand: B&R (Becko GmbH & Co. KG, Austria)
Product Type: aPCI Multi-Interface Communication Module
B&R ID Code: 0x13E4
Installation Method: Controller-specific aPCI slot (such as CP360 series)
Matching Terminals: X2X Link uses 0TB704.9 (screw type) / 0TB704.91 (push-pull type); RS232 is integrated 9-pin D-sub jack
Protection Level: IP20 (EN 60529)
Certifications: CE, UKCA, cULus, EAC, KC
Dimensions: 170 mm × 30 mm × 110 mm
Weight: Approximately 0.13 kg
Operating Temperature: 0 - 60°C
Storage Temperature: -25 - 70°C
Relative Humidity: 5% - 95% (no condensation)
Interface and Bus Specifications
IF1 - RS232 Serial Port
Connector: 9-pin D-sub jack
Maximum Transmission Distance: 900 m
Transmission Rate: Up to 115.2 kbit/s
Electrical Isolation: None
Function: Connect serial port devices (such as printers, barcode scanners, third-party instruments), support point-to-point asynchronous communication.
IF2 - X2X Link Master Station 1
Bus Type: X2X Link Master Station (Becko's dedicated high-speed fieldbus)
Connector: 4-pin male multi-point connector
Maximum Stations: 253
Network Topology: Linear
Station Distance: Maximum 100 m
Terminal Resistor: Built-in
Bus Power Supply: None
Electrical Isolation: Isolation between PLC side and interface side
Function: Manage X20/X67 I/O, servo drives, and transmit real-time control and status data.
IF3 - X2X Link Master Station 2
Bus Type: X2X Link Master Station
Connector: 4-pin male multi-point connector
Maximum Stations: 253
Network Topology: Linear
Station Distance: Maximum 100 m
Terminal Resistor: Built-in
Bus Power Supply: None
Electrical Isolation: Isolation between PLC side and interface side; Isolation between IF2 and IF3; Common ground between IF1 and PLC
Insulation Strength: Complies with industrial standards, suitable for strong electromagnetic interference environments
Status and Diagnosis
LED Indicator Lights: IF1 has 2 lights (Tx/Rx); IF2 and IF3 each have 2 lights (Tx/Rx), respectively indicating data reception and transmission status
Diagnostic Function: Through LED and Automation Studio, can monitor the communication status of the three interfaces, link quality, station connection, and fault codes, supporting rapid location of communication interruptions, offline stations, etc.
Core Functions Three-interface integration: Dual X2X Link master station + RS232. A single module realizes the integration of multiple buses and serial ports, simplifying the system architecture.
Dual bus isolation networking: The two X2X Link lines are isolated from each other, allowing independent control of I/O or drivers for different areas, and supporting redundancy and partition control.
High-speed real-time communication: X2X Link has low latency and high synchronization, meeting the motion control requirements such as multi-axis linkage and high-speed I/O acquisition.
RS232 flexible expansion: RS232 is compatible with third-party serial port devices, enhancing system compatibility and scalability.
Industrial-grade reliability: Wide temperature operation, multi-channel electrical isolation, built-in terminal resistors, suitable for harsh environments such as machine tools and workshops.
Seamless integration of B&R system: Fully compatible with 2005 series CPUs, X20/X67 I/O, and servo drives, unified configuration and programming in Automation Studio.
Application fields
Multi-axis linkage CNC system (dual bus control servo drives)
Distributed I/O partition control (two X2X Link buses are independently networked)
Automation production lines requiring RS232 integration of third-party devices
Mechanical automation (machine tools, textile, printing, packaging equipment)
Process automation (water treatment, HVAC, small-scale chemical industry)
B&R 2005 system multi-interface expansion scenario
Get a Quote