Technical Specifications
Part Number: 51304439-125 (51304439125)
Module Type: MU-TDIA12 (Digital Input FTA)
Channel Configuration: 32 × galvanically isolated digital input channels
Input Voltage: 120 VAC ±10%, 50/60 Hz
Input Type: Dry contact or wet AC voltage
Isolation: 1500 VAC rms (channel‑to‑backplane)
Response Time: ≤10 ms per channel
Power Supply: 24 VDC ±10%, 0.5 A (backplane‑powered)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 307 × 120 × 50 mm (12‑inch size B)
Weight: ~1.3 kg
Certifications: CE‑compliant, Non‑UL
Coating: Non‑conformal coated (standard environment only)
Terminals: Compression‑type (14–22 AWG)
Status Indicators: Power/Fault LED, channel status LEDs
Current Draw: ≤3 W
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)
Field Interface: Compression terminals (32 channels for 120 VAC inputs)
Redundancy: Non‑redundant (single‑controller operation)
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN
Wiring: Accepts 14–22 AWG stranded copper wire
Connector: UCN 96‑pin edge connector
Core Functions
AC Digital Input Monitoring: Captures 120 VAC discrete signals from switches, relays, and contactors.
Galvanic Isolation: Protects DCS from high‑voltage transients, ground loops, and electrical noise.
Field Termination: Centralizes 32‑channel AC digital wiring to DCS IOPs.
Status Indication: LED per channel for quick fault/status visualization.
Noise Immunity: Designed for industrial AC environments with high electrical interference.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (standard areas, CE‑required).
AC Device Monitoring: Limit switches, motor starters, relay contacts, and panel status lights (120 VAC).
General Industrial Environments: Non‑harsh areas with normal humidity, dust, and temperature conditions.
CE‑Certified Installations: Cost‑effective solutions for sites requiring CE compliance (non‑UL).
Legacy TDC3000/TPS Systems: Replacement or expansion of existing UCN‑based DCS.
Key Differences: 51304439 Series Variants
| Feature | 51304439-100 (MU-TDIA12) | 51304439-125 (MU-TDIA12) | 51304439-175 (MC-TDIA12) |
|---|---|---|---|
| Revision | 100 | 125 | 175 |
| Series | MU-TDIA12 | MU-TDIA12 | MC-TDIA12 |
| Conformal Coating | ❌ No | ❌ No | ✅ Yes |
| CE Certified | ❌ No | ✅ Yes | ✅ Yes |
| UL Certified | ❌ No | ❌ No | ✅ Yes |
| Input Voltage | 120 VAC | 120 VAC | 120 VAC |
| Channels | 32 | 32 | 32 |
| Environment | Standard (Non‑CE) | Standard (CE‑Only) | Harsh (CE/UL) |
| Cost | Lowest | Medium | Highest |
Compatibility Note
Pin‑compatible with 51304439-100 and -175; direct replacement in TDC3000/TPS UCN racks.