Honeywell 51304437-150 (MC-TAIL02)
Description
Technical Specifications
Part Number: 51304437-150 (51304437150)
Module Type: MC-TAIL02 (Low-Level Analog Input FTA)
Channel Configuration: 8 × galvanically isolated analog input channels
Input Signal Types: Thermocouple (J, K, T, E, R, S, B), RTD (PT100), Voltage (±100 mV, ±500 mV), Current (4–20 mA, external resistor)
A/D Resolution: 15 bits
Common‑Mode Voltage: 250 VAC rms or ±250 VDC (DC to 60 Hz)
Dielectric Strength: 1500 VAC rms (channel‑to‑backplane)
Power Supply: 24 VDC ±10%, 0.5 A (backplane‑powered)
Operating Temperature: -20°C to +60°C (conformal coated)
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 307 × 120 × 50 mm (12‑inch size B)
Weight: ~1.2 kg
Certifications: CE‑certified, UL‑listed
Coating: Conformal coated (dust/moisture/corrosion protection)
Terminals: Compression‑type (14–22 AWG)
Status Indicators: Power/Fault LED
Response Time: ≤100 ms per channel
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)
Field Interface: Compression terminals (8 channels for thermocouple/RTD/voltage/current)
Redundancy: Non‑redundant (single‑controller operation)
Diagnostics: On‑board self‑diagnostics with fault reporting via UCN
Wiring: Accepts 14–22 AWG stranded copper wire
Core Functions
Low‑Level Signal Conditioning: Converts and isolates weak analog signals from thermocouples, RTDs, and transmitters.
Field Termination: Centralizes low‑level analog wiring from field sensors to DCS IOPs.
Galvanic Isolation: Protects DCS from common‑mode noise, ground loops, and high‑voltage transients.
High‑Precision Conversion: 15‑bit A/D ensures accurate temperature/process variable measurement.
Harsh Environment Protection: Conformal coating defends against dust, humidity, and chemicals.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (harsh areas: high humidity, dust, corrosive fumes).
Temperature Monitoring: Thermocouple/RTD inputs for furnaces, reactors, pipelines.
Low‑Level Signal Measurement: Millivolt voltage or 4–20 mA current from pressure/level/flow transmitters.
CE/UL‑Compliant Installations: Industrial sites requiring CE/UL certification and conformal coating.
Non‑Redundant Control Systems: Standard‑availability processes without dual‑controller redundancy.
Key Differences: 51304437-150 vs -100
| Feature | 51304437-150 (MC-TAIL02) | 51304437-100 (MU-TAIL02) |
|---|---|---|
| Revision | 150 (CE/UL/Conformal Coated) | 100 (Non‑CE/Non‑Coated) |
| Series | MC-TAIL02 | MU-TAIL02 |
| Conformal Coating | ✅ Yes | ❌ No |
| CE Certified | ✅ Yes | ❌ No |
| UL Certified | ✅ Yes | ❌ No |
| Terminals | Compression | Compression |
| Redundancy | ❌ No | ❌ No |
| Environment | Harsh | Standard |
| Cost | Higher | Lower |
Compatibility Note
Pin‑compatible with 51304437-100; direct replacement in TDC3000/TPS UCN racks.