Product Introduction Model: 51304437-150 (Alias: 51304437150, MC-TAIL02) Type: Low-Level Analog Input FTA (Field Termination Assembly) Manufacturer: Honeywell Series: TDC3000 / TPS UCN DCS, MC Series I/O Description: The 51304437-150 (MC-TAIL02) is an 8‑channel low‑level analog input FTA for Honeywell TDC3000/TPS UCN systems. It is the CE‑certified, UL‑listed, conformal‑coated variant of the 51304437 series, built for harsh industrial environments requiring full agency compliance.

Description

Technical Specifications

  • Part Number: 51304437-150 (51304437150)

  • Module Type: MC-TAIL02 (Low-Level Analog Input FTA)

  • Channel Configuration: 8 × galvanically isolated analog input channels

  • Input Signal Types: Thermocouple (J, K, T, E, R, S, B), RTD (PT100), Voltage (±100 mV, ±500 mV), Current (4–20 mA, external resistor)

  • A/D Resolution: 15 bits

  • Common‑Mode Voltage: 250 VAC rms or ±250 VDC (DC to 60 Hz)

  • Dielectric Strength: 1500 VAC rms (channel‑to‑backplane)

  • Power Supply: 24 VDC ±10%, 0.5 A (backplane‑powered)

  • Operating Temperature: -20°C to +60°C (conformal coated)

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 307 × 120 × 50 mm (12‑inch size B)

  • Weight: ~1.2 kg

  • Certifications: CE‑certified, UL‑listed

  • Coating: Conformal coated (dust/moisture/corrosion protection)

  • Terminals: Compression‑type (14–22 AWG)

  • Status Indicators: Power/Fault LED

  • Response Time: ≤100 ms per channel

Interface & Communication Configuration

  • DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)

  • Field Interface: Compression terminals (8 channels for thermocouple/RTD/voltage/current)

  • Redundancy: Non‑redundant (single‑controller operation)

  • Diagnostics: On‑board self‑diagnostics with fault reporting via UCN

  • Wiring: Accepts 14–22 AWG stranded copper wire

Core Functions

  1. Low‑Level Signal Conditioning: Converts and isolates weak analog signals from thermocouples, RTDs, and transmitters.

  2. Field Termination: Centralizes low‑level analog wiring from field sensors to DCS IOPs.

  3. Galvanic Isolation: Protects DCS from common‑mode noise, ground loops, and high‑voltage transients.

  4. High‑Precision Conversion: 15‑bit A/D ensures accurate temperature/process variable measurement.

  5. Harsh Environment Protection: Conformal coating defends against dust, humidity, and chemicals.

Application Scenarios

  • Process Industries: Chemical, petrochemical, power generation, pulp & paper (harsh areas: high humidity, dust, corrosive fumes).

  • Temperature Monitoring: Thermocouple/RTD inputs for furnaces, reactors, pipelines.

  • Low‑Level Signal Measurement: Millivolt voltage or 4–20 mA current from pressure/level/flow transmitters.

  • CE/UL‑Compliant Installations: Industrial sites requiring CE/UL certification and conformal coating.

  • Non‑Redundant Control Systems: Standard‑availability processes without dual‑controller redundancy.

Key Differences: 51304437-150 vs -100

Feature51304437-150 (MC-TAIL02)51304437-100 (MU-TAIL02)
Revision150 (CE/UL/Conformal Coated)100 (Non‑CE/Non‑Coated)
SeriesMC-TAIL02MU-TAIL02
Conformal Coating✅ Yes❌ No
CE Certified✅ Yes❌ No
UL Certified✅ Yes❌ No
TerminalsCompressionCompression
Redundancy❌ No❌ No
EnvironmentHarshStandard
CostHigherLower

Compatibility Note

  • Pin‑compatible with 51304437-100; direct replacement in TDC3000/TPS UCN racks.

  • Recommended for new non‑redundant installations in harsh environments requiring CE/UL compliance.