Honeywell 51304437-100 (MU-TAIL02)
Description
Technical Specifications
Part Number: 51304437-100 (51304437100)
Module Type: MU-TAIL02 (Low-Level Analog Input FTA)
Channel Configuration: 8 × galvanically isolated analog input channels
Input Signal Types: Thermocouple (J, K, T, E, R, S, B), RTD (PT100), Voltage (±100 mV, ±500 mV), Current (4–20 mA, with external resistor)
A/D Resolution: 15 bits
Common-Mode Voltage (CMV): 250 VAC rms or ±250 VDC (DC to 60 Hz)
Dielectric Strength: 1500 VAC rms (channel-to-backplane)
Power Supply: 24 VDC ±10%, 0.5 A (backplane-powered)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non-condensing
Dimensions (H×W×D): 307 × 120 × 50 mm (12-inch size B)
Weight: ~1.2 kg
Certifications: Non-CE, Non-UL
Coating: Non-conformal coated (standard environment only)
Terminals: Compression-type terminals (14–22 AWG)
Status Indicators: Power/Fault LED
Response Time: ≤100 ms per channel
Interface & Communication Configuration
DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)
Field Interface: Compression terminals (8 channels for thermocouple/RTD/voltage/current)
Redundancy: Non-redundant (single-controller operation)
Diagnostics: On-board self-diagnostics with fault reporting via UCN
Wiring: Accepts 14–22 AWG stranded copper wire
Core Functions
Low-Level Signal Conditioning: Converts and isolates weak analog signals from thermocouples, RTDs, and transmitters.
Field Termination: Centralizes low-level analog wiring from field sensors to DCS IOPs.
Galvanic Isolation: Protects DCS from common-mode noise, ground loops, and high-voltage transients.
High-Precision Conversion: 15-bit A/D conversion ensures accurate measurement of temperature and process variables.
Signal Compatibility: Supports multiple sensor types (thermocouple, RTD, voltage, current) for versatile applications.
Application Scenarios
Process Industries: Chemical, petrochemical, power generation, pulp & paper (standard areas, non-CE).
Temperature Monitoring: Thermocouple/RTD inputs for furnace, reactor, and pipeline temperature control.
Low-Level Signal Measurement: Millivolt-level voltage or 4–20 mA current from pressure/level/flow transmitters.
General Industrial Environments: Non-harsh areas with normal humidity, dust, and temperature conditions.
Non-Certified Installations: Cost-effective solutions for sites not requiring CE/UL compliance.
Key Differences: 51304437-100 vs -150
| Feature | 51304437-100 (MU-TAIL02) | 51304437-150 (MC-TAIL02) |
|---|---|---|
| Revision | 100 (Non-CE/Non-Coated) | 150 (CE/UL/Conformal Coated) |
| Series | MU-TAIL02 | MC-TAIL02 |
| Conformal Coating | ❌ No | ✅ Yes |
| CE Certified | ❌ No | ✅ Yes |
| UL Certified | ❌ No | ✅ Yes |
| Terminals | Compression | Compression |
| Redundancy | ❌ No | ❌ No |
| Environment | Standard | Harsh |
| Cost | Lower | Higher |
Compatibility Note
Pin-compatible with 51304437-150; direct replacement in TDC3000/TPS UCN racks.
Recommended for new non-redundant installations in standard, non-CE environments (cost-effective).