Honeywell 51304431-100 (MU-TDIA22)
May 28, 2026

Honeywell 51304431-100 (MU-TDIA22)

Product Introduction Model: 51304431-100 (Alias: 51304431100, MU-TDIA22) Type: 32-Channel Digital Input FTA (Field Termination Assembly) Manufacturer: Honeywell Series: TDC3000 / TPS UCN DCS, MU Series I/O Description: The 51304431-100 (MU-TDIA22) is a 32-channel 240VAC digital input FTA for Honeywell TDC3000/TPS UCN systems. It is the non-CE, non-conformal coated, compression-terminal redundant variant of the 51304431 series, designed for standard industrial environments.

Description

Technical Specifications

  • Part Number: 51304431-100 (51304431100)

  • Module Type: MU-TDIA22 (Digital Input FTA)

  • Channel Configuration: 32 × isolated digital input channels (redundant)

  • Input Voltage Range: 120/240 VAC ±10%, 50/60 Hz

  • Input Current: 10 mA nominal per channel (at 240 VAC)

  • Isolation: 1500 VAC rms channel-to-backplane isolation

  • Logic Compatibility: UCN HPM/APM controller digital input logic

  • Power Supply: 24 VDC ±10%, 0.8 A (backplane-powered)

  • Fuse: 5 A SB (system board fuse, non-replaceable in field)

  • Operating Temperature: -20°C to +60°C

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non-condensing

  • Dimensions (H×W×D): 307 × 120 × 50 mm (12-inch size B)

  • Weight: ~1.9 kg

  • Certifications: Non-CE, non-UL, non-RoHS

  • Coating: Non-conformal coated (standard environment only)

  • Terminals: Compression-type terminals (14–22 AWG)

  • Status Indicators: 32 channel LEDs + Power/Fault LEDs

  • Response Time: ≤15 ms per channel

Interface & Communication Configuration

  • DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)

  • Field Interface: Compression terminals (32 channels: Line + Neutral)

  • Redundancy: Redundant (dual-controller input support)

  • Diagnostics: On-board self-diagnostics with fault reporting via UCN

  • Wiring: Accepts 14–22 AWG stranded copper wire

Core Functions

  1. AC Digital Input Monitoring: 32 isolated channels for 120/240 VAC field device status (switches, relays, contactors).

  2. Field Termination: Centralizes AC digital input wiring from field devices to DCS IOPs.

  3. Electrical Isolation: Protects DCS from high-voltage AC spikes, noise, and ground loops.

  4. Redundant Operation: Supports dual-controller redundancy for high-availability systems.

  5. Status Visualization: Per-channel LEDs for instant visual verification of input state.

Application Scenarios

  • Process Industries: Chemical, petrochemical, oil & gas, power generation, pulp & paper (standard areas).

  • Field Device Monitoring: AC switches, limit switches, relay contacts, motor starters, and alarm contacts (120/240 VAC).

  • High-Voltage Input Systems: Monitoring of AC-powered field devices in non-harsh environments.

  • Redundant Control Systems: Critical processes requiring dual-controller redundancy.

  • Standard Environments: Clean, dry industrial areas (no conformal coating needed).

Key Differences: 51304431-100 vs -125/-175/-200/-275

Feature51304431-100 (MU-TDIA22)51304431-125 (MU-TDIA22)51304431-175 (MC-TDIA22)51304431-200 (MU-TDIA62)51304431-275 (MC-TDIA62)
Revision100 (Non-CE/Comp)125 (CE/Comp)175 (CE/UL/CC)200 (Non-CE/Screw)275 (CE/UL/CC/Screw)
SeriesMU-TDIA22MU-TDIA22MC-TDIA22MU-TDIA62MC-TDIA62
Conformal Coating❌ No❌ No✅ Yes❌ No✅ Yes
CE/UL Certified❌ No✅ Yes✅ Yes❌ No✅ Yes
TerminalsCompressionCompressionCompressionScrewScrew
Redundancy✅ Yes✅ Yes✅ Yes✅ Yes✅ Yes
EnvironmentStandardStandardHarshStandardHarsh
CostLowestStandardHigherLowestHighest

Compatibility Note

  • Fully pin-compatible with 51304431-125/-175/-200/-275; direct drop-in for TDC3000/TPS UCN racks.

  • Recommended for new redundant installations in standard environments (lowest cost option).


Get a Quote