Honeywell 51304427-250 (MC-TDOR62)
May 28, 2026

Honeywell 51304427-250 (MC-TDOR62)

Product Introduction Model: 51304427-250 (Alias: 51304427250, MC-TDOR62) Type: Digital Output FTA (Field Termination Assembly) Relay Module Manufacturer: Honeywell Series: TDC3000 / TPS UCN DCS, MC Series I/O (Revised MU) Description: The 51304427-250 (MC-TDOR62) is a 16‑channel digital output relay FTA for Honeywell TDC3000/TPS UCN systems. It is the CE/UL‑certified, conformal‑coated upgrade of the 51304427-200 (MU-TDOR62), designed for standard‑to‑harsh industrial environments with compliance requirements

Description

Technical Specifications

  • Part Number: 51304427-250 (51304427250)

  • Module Type: MC-TDOR62 (Digital Output Relay FTA)

  • Channel Configuration: 16 × SPDT (Form C) relay outputs, independent

  • Contact Rating: 240 VAC / 125 VDC, 5 A resistive per channel

  • Isolation: 1500 VAC rms channel‑to‑backplane isolation

  • Input Logic: 24 VDC from UCN HPM/APM controller

  • Power Supply: 24 VDC ±10%, 1.0 A (backplane‑powered)

  • Fuse: 6 A SB (system board fuse, replaceable)

  • Operating Temperature: -20°C to +60°C

  • Storage Temperature: -40°C to +85°C

  • Humidity: 5%–95% RH, non‑condensing

  • Dimensions (H×W×D): 307 × 120 × 50 mm (12‑inch size B)

  • Weight: ~2.1 kg

  • Certifications: CE, UL, RoHS (-200 non‑certified)

  • Coating: Conformal coated (dust/moisture/corrosion protection)

  • Terminals: Compression‑type screw terminals (14–22 AWG)

  • Status Indicators: 16 channel LEDs + Power/Fault LEDs

  • Response Time: ≤10 ms per relay

Interface & Communication Configuration

  • DCS Interface: UCN backplane edge connector (1 Mbps, TDC3000/TPS compatible)

  • Field Interface: Screw terminals (16 channels: Common + NC + NO)

  • Redundancy: Non‑redundant (no dual‑controller input support)

  • Diagnostics: On‑board self‑diagnostics with fault reporting via UCN

  • Wiring: Accepts 14–22 AWG stranded copper wire

Core Functions

  1. Relay Output Switching: 16 independent SPDT relays for on/off control of field loads (valves, pumps, solenoids).

  2. Field Termination: Centralizes digital output wiring from DCS IOPs to field devices.

  3. Electrical Isolation: Protects DCS from field‑side voltage spikes, noise, ground loops.

  4. Status Monitoring: Per‑channel LEDs for instant visual output state verification.

  5. Compliant & Harsh‑Ready: Conformal coating + CE/UL for reliable operation in damp/dusty areas.

Application Scenarios

  • Process Industries: Chemical, petrochemical, oil & gas, power generation, pulp & paper.

  • Field Device Control: Valves, pumps, fans, motors, solenoids (≤5 A).

  • Alarm Systems: Audible/visual alarm drivers for process events.

  • Interlock Circuits: Non‑safety interlocks (non‑SIL rated).

  • Harsh/Compliant Environments: Outdoor, high‑humidity, or CE/UL‑required installations.

Key Differences: 51304427-250 vs -100/-150/-200

Feature51304427-250 (MC-TDOR62)51304427-200 (MU-TDOR62)51304427-150 (MC-TDOR22)51304427-100 (MU-TDOR22)
Revision250 (Certified/Coated)200 (Screw/Non‑CE)150 (CE/Coated)100 (Original/Non‑CE)
SeriesMC-TDOR62MU-TDOR62MC-TDOR22MU-TDOR22
Conformal Coating✅ Yes❌ No✅ Yes❌ No
CE/UL Certified✅ Yes❌ No✅ Yes❌ No
TerminalsScrewScrewScrewScrew
EnvironmentHarsh/CompliantStandardHarshStandard
CostMid‑HighLowestHigherStandard

Compatibility Note

  • Fully pin‑compatible with 51304427-100/150/200; direct drop‑in for TDC3000/TPS UCN racks.

  • Recommended for new compliant/harsh projects or -200 upgrades needing certification/coating.


Get a Quote