Honeywell 51304427-200 (MU-TDOR62)
Description
Technical Specifications
Part Number: 51304427-200 (51304427200)
Module Type: MU-TDOR62 (Digital Output Relay FTA)
Channel Configuration: 16 × SPDT relay outputs (independent)
Contact Rating: 240 VAC / 125 VDC, 5 A resistive per channel
Isolation: 1500 VAC rms channel‑to‑backplane isolation
Input Logic: 24 VDC from UCN HPM/APM controller
Power Supply: 24 VDC ±10%, 1.0 A (backplane‑powered)
Fuse: 6 A SB (system board fuse, non‑replaceable in field)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 307 × 120 × 50 mm (12‑inch size B)
Weight: ~2.0 kg
Certifications: Non‑CE, non‑UL, non‑RoHS
Coating: Non‑conformally coated (standard environment only)
Terminals: Compression‑type screw terminals (14–22 AWG)
Status Indicators: 16 channel LEDs + Power/Fault LEDs
Response Time: ≤10 ms (per relay)
Interface & Communication Configuration
DCS Interface: UCN backplane via edge connector (1 Mbps, TDC3000/TPS compatible)
Field Interface: Screw terminals (16 channels: common + NC + NO)
Redundancy: Non‑redundant (no dual‑controller input support)
Diagnostics: On‑board self‑diagnostics with fault reporting to DCS via UCN
Core Functions
Relay Output Switching: 16 independent SPDT relays for on/off control of field loads (valves, pumps, solenoids).
Field Termination: Centralizes digital output wiring from DCS IOPs to field devices via screw terminals.
Electrical Isolation: Protects DCS from field‑side voltage spikes, noise, and ground loops.
Status Monitoring: Per‑channel LEDs for instant visual verification of output state.
Cost‑Effective Operation: Uncoated, non‑certified design reduces cost for standard industrial environments.
Application Scenarios
Process Industries: Chemical, petrochemical, oil & gas, power generation, pulp & paper (non‑harsh areas).
Field Device Control: On/off control of valves, pumps, fans, motors, and solenoids (≤5 A).
Alarm Systems: Driving audible/visual alarms for process events.
Interlock Circuits: Non‑safety interlocks (non‑SIL rated) for process control.
Standard Environments: Ideal for clean, dry industrial areas (no conformal coating needed).
Key Differences: 51304427-200 vs 51304427-100/150
| Feature | 51304427-200 (MU-TDOR62) | 51304427-100 (MU-TDOR22) | 51304427-150 (MC-TDOR22) |
|---|---|---|---|
| Revision | 200 (Screw, Non‑CE) | 100 (Original, Non‑CE) | 150 (Updated, CE/UL) |
| Series | MU‑TDOR62 | MU‑TDOR22 | MC‑TDOR22 |
| Terminals | Screw | Screw | Screw |
| Conformal Coating | ❌ No | ❌ No | ✅ Yes |
| CE/UL Certified | ❌ No | ❌ No | ✅ Yes |
| Cost | Lowest | Standard | Higher |
| Environment | Standard (Clean/Dry) | Standard | Harsh (Damp/Dusty) |
Compatibility Note
Fully pin‑compatible with 51304427-100/150; direct drop‑in replacement for TDC3000/TPS UCN racks.
Recommended for new installations in standard environments (lowest cost option).
Get a Quote