Honeywell 51304423-100 (MU-TDOD12)
Description
Technical Specifications
Part Number: 51304423-100 (51304423100)
Module Type: MU-TDOD12 (Digital Output, 12‑Channel)
Relay Configuration: 12 × SPDT (Single‑Pole Double‑Throw) relays
Contact Rating: 120/240 VAC, 5 A resistive; 30 VDC, 5 A
Isolation: 1500 VAC rms channel‑to‑backplane isolation
Input Logic: 24 VDC from UCN controller (HPM/APM)
Power Supply: 24 VDC ±10%, 0.8 A (backplane‑powered)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 270 × 185 × 95 mm
Weight: ~2.4 kg
Certifications: CE, UL, RoHS
Status Indicators: LED per channel (ON/OFF) + Power/Fault LEDs
Interface & Communication Configuration
DCS Interface: UCN backplane (1 Mbps) via edge connector
Field Interface: Screw terminals (12 channels, common + NC + NO)
Redundancy: Supports redundant HPM/APM controller inputs
Diagnostics: On‑board self‑diagnostics with fault reporting to DCS
Core Functions
Isolated Relay Outputs: 12 independent SPDT relays for direct field control.
High‑Power Switching: Drives AC/DC loads up to 5 A (valves, motors, solenoids).
Electrical Isolation: Protects DCS from field‑side voltage spikes and noise.
Status Monitoring: Per‑channel LEDs for quick visual verification of output state.
Rack Integration: Standard TDC3000 rack‑mount design for easy installation.
Application Scenarios
Process Industries: Chemical, petrochemical, oil & gas, power generation, pulp & paper.
Field Device Control: On/off control of valves, pumps, fans, motors, and solenoids.
Alarm Systems: Driving audible/visual alarms for process events.
Interlock & ESD: Safety interlocks and emergency shutdown circuits.
Key Difference vs. 51304421-100/200
51304423-100 (MU-TDOD12): 12‑channel relay module (standalone, rack‑mount), higher density than PLCG panels.
51304421-100/200: PLCG relay panel/card (fewer channels, panel‑mount).
Get a Quote