Description
Technical Specifications
Part Number: 51304362-350 (51304362350)
Alternate Model: MC‑PSIM11
Channel Count: 2 fully isolated serial channels
Interface Standards: EIA‑232 (RS‑232), EIA‑422 (RS‑422), EIA‑485 (RS‑485)
Baud Rate: 300–115.2 kbps (per‑channel configurable; high‑speed mode supported)
Data Format: 7/8 data bits, 1/2 stop bits, odd/even/no parity
Signal Isolation: 250 Vrms channel‑to‑channel; 500 Vrms field‑to‑backplane
Power Supply: 24 VDC ±10%, 5–7 W typical (HPM power supply compatible)
Operating Temperature: -40°C to +70°C
Storage Temperature: -55°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Dimensions (H×W×D): 308 × 120 × 35 mm
Weight: 0.58 kg (1.28 lbs)
Certifications: CE, UL, RoHS; conformally coated for harsh industrial environments
Interface & Communication Configuration
Field Interface: Dual DB25 ports (or compression ports); compatible with Honeywell FTA (Field Terminal Assembly) for direct device wiring.
System Interface: Dedicated UCN backplane connector (1 Mbps UCN communication).
Supported Protocols: ASCII, Modbus RTU/ASCII, and custom serial protocols (configurable via system software).
Diagnostics: On‑board LEDs for power, run, fault, and communication status; real‑time reporting of framing/parity errors, timeouts, and channel‑level faults.
Redundancy: Not supported (single‑module operation only).
Core Functions
2‑Channel High‑Speed Serial Bridging: Connects DCS controllers to third‑party serial devices with baud rates up to 115.2 kbps for low‑latency data exchange.
Multi‑Protocol Support: Handles ASCII, Modbus RTU/ASCII, and custom protocols for flexible integration with diverse field devices.
Enhanced Electrical Isolation: 250 Vrms channel‑to‑channel isolation suppresses noise and ground loops in harsh industrial environments.
Real‑Time Diagnostics: Detects and reports communication errors (framing, parity, timeout) and channel faults for rapid troubleshooting.
Conformal Coating: Protected against dust, moisture, and chemical vapors for reliable operation in extreme conditions.
UCN High‑Speed Communication: Transfers serial data to the DCS controller via 1 Mbps UCN backplane for real‑time process monitoring.
Application Scenarios
Process Industries: Chemical, petrochemical, oil & gas, power generation, pulp & paper, pharmaceuticals, water treatment.
Third‑Party Device Integration: Connects DCS to PLCs, flow meters, gas analyzers, temperature controllers, and serial printers.
Legacy System Upgrades: Interfaces older serial devices with modern Honeywell TDC3000/TPS/Experion PKS DCS.
High‑Speed Data Logging & Printing: Enables DCS to send high‑volume process data to serial printers or loggers for record‑keeping.
Get a Quote