Honeywell 51304337-250 (MC-TAIH52)
May 27, 2026

Honeywell 51304337-250 (MC-TAIH52)

Honeywell 51304337-250 (MC-TAIH52) – Full Data (English) Product Introduction Model: 51304337-250 (Alias: MC-TAIH52) Type: Redundant STI High-Level Analog Input Module Manufacturer: Honeywell Series: TDC3000 / HPM (High-Performance Process Manager) DCS System Description: The MC-TAIH52 is a 16-channel redundant high-level analog input module with integrated STI (Signal Termination Interface), designed for Honeywell TDC3000/HPM DCS. It collects 4–20mA / 1–5V signals from field transmitters and sensors, converting them into digital data for process control.

Description

Technical Specifications

  • Part Number: 51304337-250 (Rev D/M/V)

  • Channel Count: 16 isolated analog inputs

  • Input Signal Ranges:

    • Current: 4–20mA, 0–20mA

    • Voltage: 1–5V, -10V to +10V

  • Input Impedance: >2MΩ (voltage), 250Ω (current)

  • Accuracy: ±0.075% of full scale (25°C)

  • Resolution: 16-bit ADC

  • Sampling Rate: 4 samples/sec per channel (all channels within 250ms window)

  • Redundancy: 1:1 redundant pairing supported, automatic failover

  • Power Supply: 24VDC ±10%, 55mA typical

  • Operating Temperature: -40°C to +70°C

  • Storage Temperature: -55°C to +85°C

  • Humidity: 5%–95% RH, non-condensing

  • Dimensions (H×W×D): 308 × 120 × 35 mm

  • Weight: 0.48–0.5 kg

  • Certifications: CE, UL, RoHS, CO, CQ

Interface & Communication Configuration

  • Field Interface: Integrated STI compression termination (direct screw-terminal wiring, no external FTA needed)

  • System Interface: 2× high-density backplane connectors for HPM bus

  • Communication Protocol: Proprietary Honeywell HPM bus (TDC3000), redundant data transmission

  • Isolation: Channel-to-channel 250Vrms; field-to-system 500Vrms

  • Diagnostics: On-board LEDs for power, run, fault, redundancy status; real-time fault reporting via HPM bus

Core Functions

  1. 16-Channel High-Precision Acquisition: 16-bit resolution, ±0.075% accuracy for 4–20mA/1–5V field signals。

  2. Redundant Operation: 1:1 redundancy for critical loops; automatic failover on primary fault, bumpless transfer.

  3. Integrated STI Termination: Built-in compression terminals eliminate external FTA, reduce wiring complexity and cost。

  4. Signal Conditioning: On-board filtering, amplification, linearization for noisy industrial environments.

  5. Comprehensive Diagnostics: Detects overrange, open/short circuit, module health; reports to DCS.

  6. Hot-Swappable: Online replacement in redundant mode, no system shutdown.

Application Scenarios

  • Process Industries: Chemical, petrochemical, oil & gas, power generation, pulp & paper.

  • Critical Parameter Monitoring: Flow, pressure, temperature, level, vibration from transmitters/sensors.

  • Redundant DCS Systems: Safety-critical loops requiring high availability (reactor control, boiler protection).

  • Honeywell TDC3000 / Experion PKS: Native compatibility for seamless integration.