51304337150
Description
Technical Specifications
Part Number: 51304337-150 (Rev V)
Channel Count: 16 isolated analog inputs
Input Signal Ranges:
Current: 4–20mA, 0–20mA
Voltage: 1–5V, -10V to +10V
Input Impedance: >2MΩ (voltage), 250Ω (current)
Accuracy: ±0.05% of full scale (25°C)
Resolution: 16-bit ADC
Sampling Rate: 20Hz per channel
Redundancy: Supported (1:1 redundant pairing)
Power Supply: 24VDC ±10%, 50mA typical
Operating Temperature: -40°C to +70°C
Storage Temperature: -55°C to +85°C
Humidity: 5%–95% RH, non-condensing
Dimensions (H×W×D): 308 × 120 × 35 mm
Weight: 0.4 kg (400g)
Certifications: CE, UL, RoHS, CO, CQ
Interface & Communication Configuration
Field Interface: STI (Compression Termination) FTA – screw-terminal block for direct field wiring
System Interface: 2× high-density connectors for HPM backplane communication
Communication Protocol: Proprietary Honeywell HPM bus (TDC3000 system), supports redundant data transmission
Isolation: Channel-to-channel isolation (250Vrms), field-to-system isolation (500Vrms)
Diagnostics: On-board LED indicators for power, status, fault, and redundancy health
Core Functions
High-Precision Analog Acquisition: Converts 4–20mA/1–5V field signals to digital data with 16-bit resolution and ±0.05% accuracy.
Redundant Operation: Supports 1:1 redundancy for critical loops; automatic failover on primary module fault.
Signal Conditioning: Built-in filtering, amplification, and linearization for noisy industrial environments.
STI Termination: Integrated compression terminals eliminate external FTA modules, reducing wiring complexity.
Fault Diagnostics: Real-time monitoring of input overrange, open/short circuit, and module health; reports to DCS via HPM bus.
Hot-Swappable: Can be replaced online without system shutdown (redundant mode).
Application Scenarios
Process Control Industries: Chemical, petrochemical, oil & gas, power generation (thermal/ nuclear), pulp & paper.
Critical Parameter Monitoring: Flow, pressure, temperature, level, and vibration measurements from transmitters/sensors.
Redundant DCS Systems: Safety-critical loops requiring high availability (e.g., reactor control, boiler protection).
Honeywell TDC3000 / Experion PKS: Native compatibility with Honeywell’s flagship DCS platforms for seamless integration.
Get a Quote