51304335200
Description
Overview
The 51304335‑200 (MU‑TAOX52) is a screw‑terminal, redundant‑capable AO FTA that mates with the MC‑TAOX52 IOP module. It provides field‑side termination, signal conditioning, and 1:1 redundancy switching for 8 analog output channels in Honeywell’s legacy DCS.
Technical Specifications
Part Number: 51304335200 / 51304335‑200
Designation: MU‑TAOX52 (8‑ch AO Redundancy FTA)
System Compatibility: Honeywell TDC 3000, TPS, Experion PKS (UCN)
Mating IOP: MC‑TAOX52 (8‑ch AO IOP, 51304335‑275)
Channels: 8 isolated analog outputs
Signal Types: 4–20 mA (default), 0–10 VDC (jumper selectable)
Termination: Screw terminals (field wiring)
Redundancy: 1:1 automatic failover (primary/secondary IOP)
Backplane Voltage: 5 VDC
Field Power: 24 VDC (external)
Operating Temp: 0°C to +60°C
Humidity: 5%–95% non‑condensing
Dimensions (W×H×D): ~307 × 120 × 35 mm (Size B, 12 in)
Weight: ~0.48 kg
Conformal Coating: No (not coated)
CE Compliance: No
Key Features
8‑Channel Screw Terminal: Direct, reliable field wiring for 8 AO loops.
Redundancy Switching: Automatic switchover to secondary MC‑TAOX52 IOP on fault.
Jumper‑Selectable Output: 4–20 mA / 0–10 VDC to match valve/VFD/actuator requirements.
LED Status Indicators: Power, channel, fault, and redundancy mode LEDs.
Hot‑Swap Compatible: Replaceable without system shutdown.
Uncoated PCB: Lower cost; for clean, non‑harsh environments.
Applications
Honeywell TDC 3000 / TPS / Experion PKS I/O cabinets
Oil & gas, petrochemical, power, pulp & paper, water treatment
8‑loop analog control (valves, actuators, VFDs)
High‑availability systems with redundant AO IOPs
Related Part Numbers
51304335‑200: MU‑TAOX52 (8‑ch AO FTA, this model)
51304335‑275: MC‑TAOX52 (8‑ch AO IOP, non‑redundant)
51304335‑125: MU‑TAOX12 (8‑ch AO FTA, coated, CE)
51304335‑175: MC‑TAOX12 (12‑ch AO IOP)
Get a Quote