Model: 51304084125 (51304084-125, MU-TPIX12, Rev. E) Manufacturer: Honeywell Type: 16‑Channel High‑Level Pulse Input FTA (Field Terminal Assembly), Extended Version Overview: Extended 16‑channel pulse input termination board for Honeywell TDC 3000 / TPS / Experion PKS UCN systems. It works with MC‑TPIX12 IOP modules, offering extra features compared to the standard 51304084‑100. Used for flow, speed, and counting pulse signals in industrial control.

Description

Technical Specifications

Part Number: 51304084125 / 51304084‑125 / MU‑TPIX12 (Rev. E)

System Compatibility: Honeywell TDC 3000, TPS, Experion PKS, UCN Network

Controllers: HPM, APM, PM

Channels: 16 isolated high‑level pulse inputs

Input Signal: 12–24 VDC, NPN/PNP, dry/wet contact

Frequency: 0–100 kHz (max)

Isolation: 2,500 Vrms (channel‑to‑backplane)

Filter: 10 μs–100 ms programmable

Input Impedance: >10 kΩ

Backplane Voltage: 5 VDC

Power Consumption: ~4 W

Operating Temp: −40°C to +85°C

Storage Temp: −55°C to +125°C

Humidity: 5%–95% non‑condensing

Dimensions (W×H×D): ~220 × 120 × 35 mm

Weight: ~400 g

Key Features (vs. 51304084‑100)

Extended I/O wiring terminals for easier field cable connection

Enhanced surge suppression on each channel for heavier EMI/RFI environments

Additional status LEDs for extended diagnostics

Rev. E hardware with component upgrades for longer service life

Same core performance: 100 kHz speed, 2,500 Vrms isolation, hot swap, redundancy support

Applications

Honeywell TDC 3000 / TPS / Experion PKS control cabinets

Oil & gas, chemical, power, pulp & paper, water treatment

High‑noise field pulse signals (flow meters, encoders, tachometers)

Critical counting/accumulation loops requiring extra surge protection

Related Part Numbers

51304084‑100: Standard 16‑channel pulse input FTA

51304084‑125: Extended 16‑channel pulse input FTA (this model)

51304084‑175: MC‑TPIX12 Pulse Input IOP module