51303979550
Description
Technical Specifications
Part Number: 51303979550 / 51303979‑550
System: Honeywell TDC 3000, TPS, Experion PKS, UCN Network
Controller Compatibility: HPM and APM (dual support)
Function: Advanced I/O Link interface, signal amplification, isolation, redundancy support
Protocol: I/O Link (250 kbps standard; 1 Mbps high‑speed for HPM)
Physical Layer: RS‑485, fully isolated
Ports: 1 local I/O Link, 1 extended I/O Link (cascadable)
Max Distance: 1,200 m (4,000 ft)
Max Nodes: 32 FTA/IOTA modules per link
Backplane Voltage: 5 VDC
Field Voltage: 24 VDC
Power Consumption: ~8 W (max 10 W)
Operating Temperature: 0°C to +60°C (extended: ‑40°C to +70°C)
Humidity: 5%–95% non‑condensing
Dimensions (W×H×D): ~220 × 120 × 35 mm
Weight: ~320 g
Key Features
Dual Controller Support: Works with both HPM (high‑speed 1 Mbps) and APM (250 kbps) controllers.
Full Redundancy: Dual‑link redundancy for maximum system availability (critical for continuous processes).
Extended Temperature Rating: Operates reliably in extreme cold (‑40°C) and heat (+70°C).
Enhanced Noise Immunity: Isolated drivers/receivers for heavy industrial EMI environments.
Comprehensive LED Diagnostics: Power, link activity, Tx/Rx, fault, and redundancy status indicators.
Hot‑Swappable: Replacement without system shutdown.
Conformal Coating: Protects against dust, moisture, and vibration.
Applications
TDC 3000 / TPS / Experion PKS control cabinets (HPM or APM slots)
Large process plants (chemical, power, oil & gas, pulp & paper)
High‑availability systems requiring I/O Link redundancy
Remote FTA/IOTA connections across long distances
Related Part Numbers (51303979 Series)
51303979‑100: Basic I/O Link Interface Card (PM/APM)
51303979‑200: Standard I/O Link Extender (PM/APM)
51303979‑400: Advanced I/O Link Interface Card (PM/APM)
51303979‑500: Advanced I/O Link Interface Card (HPM only)
51303979‑550: Advanced I/O Link Interface Card (HPM/APM Redundant)