0-57414-1
Description
1. Model Definition
0-57414: Base Modbus gateway/interface module for AutoMax DCS 5000
-1: Revision 1, early production, no conformal coating, basic firmware
2. Basic Specifications
Function: Connects AutoMax PLC rack to Modbus RTU/ASCII networks (master/slave)
Ports: 1 × RS-232/RS-485 selectable, isolated
Baud Rates: 300–19.2 kbps
Data Format: 7/8 data bits, 1/2 stop bits, odd/even/no parity
Power Supply: 5 V DC ±5% from backplane; 0.8 A typical
Operating Temperature: 0 °C to +55 °C
Storage Temperature: −40 °C to +85 °C
Dimensions (W×H×D): 32 × 298 × 187 mm
Weight: ~0.75 kg
Conformal Coating: None (Rev 1; later Rev D added coating)
Manual: J-3637 (Modbus Interface Module User Guide)
3. Interfaces & Communication
Backplane: AutoMax DCS 5000 system bus
Front Port: DB9 (RS-232/RS-485, switch selectable)
Status LEDs: Power, Ready, Tx, Rx, Fault
Isolation: 2500 V AC between Modbus port and logic
4. Key Functions
Modbus Gateway: Enables AutoMax to communicate with Modbus RTU/ASCII devices (sensors, drives, HMIs)
Master/Slave Modes: Supports both roles in Modbus network
Data Mapping: Maps AutoMax memory to Modbus registers (coils, inputs, holding registers)
Error Handling: Parity, framing, overrun error detection; bus timeout monitoring
Rev 1 Specifics: Original firmware, no environmental coating, limited diagnostic features
5. Applications
AutoMax DCS 5000 systems needing Modbus integration
Connecting legacy Reliance drives to Modbus-based SCADA/HMI
Industrial networks with mixed AutoMax and Modbus devices (conveyors, pumps, fans)
Direct replacement for 57C414-1 in older racks
6. Revision Cross-Reference
-1: Rev 1, early, no coating, basic firmware
-D: Rev D, full conformal coating, enhanced diagnostics, extended temp −10 °C to +60 °C
Get a Quote