0-57405-E
Description
Model Explanation 0-57405-E
0-57405: Basic Model (AutoMax Drive Analog I/O)
E: Hardware Revision, further optimized on the basis of -D
Full Name: Drive Analog I/O Module
Compatibility: AutoMax PLC / DCS 5000 Rack; can be directly replaced with -C / -D, no need to modify program wiring.
Technical Specifications (Official)
Manufacturer: Reliance Electric (now Rockwell Automation)
Channels: 5 Analog Inputs + 5 Analog Outputs (5AI + 5AO)
Signal Types: ±10 VDC or 4–20 mA, per channel selectable by software
Resolution: 12 bits
Isolation: Channel ↔ Backplane 2500 VAC Photoelectric Isolation
Operating Temperature: 0°C ~ +60°C (higher than -D)
Power Consumption: ≤15 W
Size: 343 × 203 × 38 mm (standard 1.25" slot)
Weight: Approximately 0.84 kg
Protection: IP20
Firmware / Manual: Corresponding Manual D-2715
Interfaces and Indicators
Backplane: AutoMax专用边缘连接器 (power, address, data)
Frontend: 10-bit screw terminal block (CH1–CH10)
Status LEDs:
OK (Green): Module is normal
FAULT (Red): Channel / Power / Communication Fault
Programming Port: TO PMI (connect programmer / debugging) Core function
5AI + 5AO Mixed Analog Input: Compatible with sensors (temperature / pressure / flow) and frequency converters / actuators.
Wide temperature range and high immunity: 0 to +60°C. Enhanced anti-interference and lightning protection design, suitable for harsh conditions.
Seamless replacement - C/D: Pin, software, and mechanical compatibility, direct upgrade without rewiring.
Hot-swappable: Replace the rack while powered on, without interrupting production.
Self-diagnosis: Fault indicator quickly locates short circuits, open circuits, and over-range.
Comparison with -C / -D (Key Differences)
-C: 0 to 50°C, basic immunity, discontinued
-D: 0 to 55°C, enhanced heat dissipation / immunity, replacement for -C
-E: 0 to 60°C, highest temperature resistance + enhanced EMC, ultimately compatible with revised version
Typical Applications
System: Reliance AutoMax / DCS 5000
Industry: Metallurgy, papermaking, water treatment, power, heavy machinery
Purpose: Frequency converter closed-loop control, temperature / pressure / flow collection, valve position control, multi-machine synchronization
Installation and Maintenance Installation
Disconnect the power supply, insert the rack slot, and lock the panel; connect ±10V or 4–20mA according to the terminal definition.
The power-on OK light will illuminate, and the CPU will automatically identify and assign the address. Maintenance
Quarterly: Check terminal fastening, LED status, cable shielding and aging.
Half-yearly: Power off and perform anti-static cleaning.
Replacement: -E Direct replacement -C/ -D, no rewiring, no parameter modification.
Get a Quote