A06B-6140-H055
Description
1. General Information
Model: A06B-6140-H055 (αiPS-55, PSM-55i)
Type: 3‑phase regenerative power supply module (Alpha i series)
Manufacturer: FANUC
Description: High‑power common DC‑bus supply for αiSV servo amplifiers and αiSP spindle amplifiers; supports heavy‑duty CNC machines, large machining centers, and high‑torque spindle applications.
Function: Provides main motor power + control power to servo units; includes regeneration (feeds deceleration energy back to the line).
Manual Reference: B‑65282EN
2. Electrical Specifications
Input: 3‑phase AC 200–240 V ±10%, 50/60 Hz
Rated Input Current: 228 A @ 200 V
Rated Input Power: 65 kW
DC Link Output: 283–339 VDC
Rated Output Current: 234 A DC
Regeneration: Built‑in (no external resistor needed)
Control Power: 24 VDC (internal, for servo logic)
Cooling: Forced air (internal fan A90L‑0001‑0441#39 + external fan A50L‑0001‑0509)
Insulation Class: Class H (180 °C)
3. Environmental & Mechanical
Operating Temp: 0 °C to +55 °C
Storage Temp: −20 °C to +70 °C
Humidity: 5–95% RH, non‑condensing
Altitude: ≤1000 m (derate 1%/100 m above)
Protection: IP20 (front)
Mounting: Vertical in cabinet; ≥100 mm clearance top/bottom
Dimensions (W×H×D): 300 mm × 350 mm × 250 mm
Weight: Approx. 20 kg (44 lbs)
4. Key Features
65 kW high‑power: For large servo/spindle combinations
Regenerative: Reduces energy waste and heat
Common DC bus: Synchronizes multiple axes, reduces wiring
Dual‑fan cooling: Heavy‑duty thermal management
Built‑in protection: Overcurrent, overvoltage, undervoltage, overtemperature, fan fault, input phase loss
LED indicators: Power, alarm, DC link ready
Diagnostics: Real‑time monitoring via FSSB
5. Installation & Wiring
Power off: Disconnect all AC power; wait ≥15 minutes for DC bus discharge.
Mounting: Secure vertically to rigid rail; maintain airflow clearances.
AC input: Connect L1/L2/L3 and PE (protective earth); use 120 mm² cables for 228 A.
DC bus: Connect DC+ / DC− to servo/spindle amplifiers; torque terminals to 2.5–3.0 N·m.
Control power: 24 VDC to CNC/servo logic.
Fans: Verify internal/external fans run on power‑on.
6. Alarm Codes (Common)
AL‑1: Main circuit overcurrent (short, ground fault, overload)
AL‑2: Cooling fan stopped (replace fan immediately)
AL‑3: Heatsink overtemperature (poor ventilation, fan blocked)
AL‑4: DC link undervoltage (input loss, phase failure)
AL‑5: Precharge failure (capacitor bank fault)
AL‑6: Input power abnormal (phase imbalance, voltage drop)
AL‑7: DC link overvoltage (regeneration overload, faulty servo)
7. Maintenance
Monthly: Clean air filters; check fan operation (replace if noisy/stuck).
Quarterly: Torque check on all power terminals; inspect cables for wear.
Annual: Test regeneration function; check DC bus capacitor ripple.
8. Safety Precautions
Only qualified electricians may install/service.
High voltage remains 15+ minutes after power‑off—risk of shock.
Do not block ventilation—fire/overheating hazard.
Use only FANUC‑specified cables/connectors.
Properly ground the module chassis.