51309136175
May 22, 2026

51309136175

51309136‑175 (MC‑TAIH03) is a Conformal Coated, CE‑Compliant High‑Level Analog Input FTA (HLAI FTA) for Honeywell TDC3000 / TPS / Experion PKS UCN systems. It provides 16‑channel field termination and signal conditioning for high‑level voltage inputs, pairing with MU‑PAIH03 / MC‑PAIH03 IOPs.

Description

51309136‑175 (MC‑TAIH03) is a Conformal Coated, CE‑Compliant High‑Level Analog Input FTA (HLAI FTA) for Honeywell TDC3000 / TPS / Experion PKS UCN systems. It provides 16‑channel field termination and signal conditioning for high‑level voltage inputs, pairing with MU‑PAIH03 / MC‑PAIH03 IOPs.

General Information

  • Part Number: 51309136‑175

  • Alternate PN: MC‑TAIH03

  • Type: High‑Level Analog Input FTA (HLAI FTA)

  • Compatible IOPs: MU‑PAIH03 (51304754‑100), MC‑PAIH03 (51304754‑150)

  • Compatible Systems: Honeywell TDC3000, TPS, Experion PKS (UCN)

  • Status: Discontinued (EOL); refurbished/used available

  • Origin: United States

  • Certification: CE compliant

  • Coating: Conformal coated (for harsh environments)

  • Dimensions: 152 mm (6 in, Size A) × 100 mm × 35 mm

  • Weight: Approx. 0.65 kg (1.43 lbs)

  • Redundancy: Non‑redundant

Technical Specifications

  • Input Channels: 16 single‑ended high‑level analog inputs

  • Signal Ranges: 0–10 VDC, ±5 VDC, ±10 VDC

  • Termination: Compression screw terminals (field wiring)

  • Connector: 50‑pin ribbon connector (to IOP)

  • Isolation: 500 VAC channel‑to‑ground

  • Power: 24 VDC (15–30 VDC), ≤3 W

  • Operating Temperature: 0°C to +55°C (32°F to 131°F)

  • Storage Temperature: -40°C to +85°C (-40°F to 185°F)

  • Humidity: 10%–90% RH, non‑condensing

Key Features

  1. Conformal Coating: Protects against moisture, dust, and chemical exposure for harsh industrial use.

  2. CE Compliance: Meets EU EMC directives for industrial electromagnetic compatibility.

  3. 16‑Channel Density: High‑density termination for 16 voltage inputs, saving cabinet space.

  4. Vibration‑Resistant Terminals: Compression screw terminals ensure stable field connections.

  5. Direct IOP Compatibility: Seamlessly mates with MU‑PAIH03 / MC‑PAIH03 analog input processors.

Applications

  • Process Industries: Chemical, petrochemical, power generation, oil & gas, pulp & paper.

  • System Role: Field termination & signal conditioning for high‑level analog inputs in Honeywell DCS.

  • Typical Uses:

    • Connecting voltage‑output pressure, flow, level, and temperature transmitters.

    • Isolating and routing analog signals to HLAI IOPs.

    • High‑precision data acquisition for critical control loops in harsh environments.

Installation & Wiring

  1. ESD Protection: Use anti‑static wristbands and ESD‑safe work surfaces.

  2. Power Off: De‑energize the I/O chassis before insertion/removal.

  3. Chassis Installation:

    • Insert FTA into Size A slot in UCN I/O chassis.

    • Secure with mounting screws.

    • Connect 50‑pin ribbon cable to mating IOP.

  4. Field Wiring:

    • Use shielded twisted‑pair cable for voltage signals.

    • Connect signal positive/negative to designated compression terminals.

    • Ground shields at one end to avoid ground loops.

  5. Configuration: Set channel ranges (0–10 V, ±10 V, etc.) via Experion PKS/TPS software.

Maintenance

  • Inspection: Check terminal tightness, cable connections, and 24 VDC power.

  • Cleaning: Use dry, soft cloth; avoid liquid cleaners.

  • Troubleshooting:

    • Verify wiring polarity and integrity.

    • Check for short circuits or ground faults.

    • Use system diagnostics to isolate faulty channels.

Safety Notes

  • Disconnect chassis power before installation/maintenance.

  • Operate within rated temperature/humidity limits.

  • Do not modify or disassemble (voids warranty).

  • Comply with site ESD and safety procedures.