51306773175
Description
Product Overview
General Information
Part Number: 51306773175 (51306773‑175)
Alternate PN: CC‑TAID01
Module Type: Analog Input FTA (Field Termination Assembly)
Compatible Systems: Honeywell TDC3000, TPS, Experion PKS (UCN)
Manufacturer: Honeywell
Status: Discontinued (EOL); new surplus, refurbished, and used units available
Origin: United States
Certification: CE, UL, CSA; conformal coated for harsh environments
Technical Specifications
Input Signals: 4–20 mA, 0–20 mA, 0–10 V, ±10 V (configurable)
Channels: 8 or 16 isolated analog inputs (model‑dependent)
Resolution: 16‑bit
Accuracy: ±0.1% full scale at 25°C
Isolation: 1500 VAC channel‑to‑channel, channel‑to‑backplane
Input Impedance: 250 Ω (current), >1 MΩ (voltage)
Power Requirement: 24 VDC (15–30 VDC), ≤5 W
Operating Temperature: ‑20°C to +60°C (‑4°F to 140°F)
Storage Temperature: ‑40°C to +85°C (‑40°F to 185°F)
Humidity: 10%–90% RH, non‑condensing
Dimensions: 140 mm × 80 mm × 50 mm
Weight: Approx. 0.75 kg
Key Features
High‑Density Isolated Inputs: Accepts multiple 4–20 mA / 0–10 V transmitter signals with full channel isolation to eliminate ground loops.
Industrial‑Grade Reliability: Conformal coated PCB, wide temperature tolerance, and robust construction for chemical, power, oil & gas, and pulp & paper plants.
Precision Signal Conditioning: 16‑bit resolution and ±0.1% accuracy ensure accurate monitoring of pressure, flow, level, and temperature.
Fault Detection: Built‑in open/short‑circuit detection for field wiring and transmitters, with LED status indicators.
Seamless Integration: Standard Series C form factor for easy installation in UCN I/O chassis; supports hot‑swapping in redundant systems.
Applications
Process Industries: Chemical, petrochemical, power generation, oil & gas, pulp & paper, pharmaceuticals.
System Role: Primary analog input interface for Honeywell UCN/TDC3000 DCS.
Typical Uses:
Monitoring pressure, flow, level, and temperature transmitters.
High‑density analog signal multiplexing in large process plants.
Accurate data acquisition for closed‑loop control systems.
Installation & Wiring
ESD Precautions: Use anti‑static wristbands and ESD‑safe work surfaces.
Power Off: De‑energize the I/O chassis before inserting/removing the module.
Chassis Installation: Insert into a UCN I/O slot and secure with mounting screws.
Field Wiring:
Connect 4–20 mA / 0–10 V transmitter wires to the compression terminals.
Use shielded twisted‑pair cable; maintain consistent cable length and polarity.
Configuration: Use Experion PKS or TPS software to set signal type, range, and scaling parameters.
Maintenance
Periodic Inspection: Check LED status, terminal tightness, and 24 VDC power supply.
Cleaning: Remove dust with a dry, soft cloth; avoid liquid cleaners.
Fault Troubleshooting:
Verify transmitter wiring integrity and polarity.
Check for open/short circuits in field cables.
Use system diagnostics to identify faulty channels or wiring.
Safety Notes
Perform all installation and maintenance with chassis power disconnected.
Operate within rated temperature and humidity limits.
Do not modify or disassemble the module; this voids the warranty and may cause damage.
Comply with site ESD and safety procedures at all times.
Get a Quote