51305907175
Description
Product Overview
Basic Information
Part Number: 51305907175 (51305907‑175)
Alternate PN: MC‑TAMR04
Module Type: Low‑Level Analog Input Mux / RTD FTA
Compatible Systems: Honeywell TDC3000, TPS, Experion PKS (UCN)
Manufacturer: Honeywell
Weight: Approx. 0.75 kg
Status: Discontinued (new/remanufactured/used available)
Certification: CE, UL, CSA; conformal coated
Technical Specifications
Input Channels: 16 fully isolated RTD inputs (expandable)
Signal Type: RTD (Platinum 100 Ω, 3‑wire/4‑wire)
Isolation: 1500 VAC channel‑to‑channel, channel‑to‑backplane
Input Range: 0–400 Ω (configurable)
Accuracy: ±0.05% full scale (25°C)
CMRR: 120 dB min (50/60 Hz, 1000 Ω source)
Power: 24 VDC (15–30 VDC), 150 mA typical
Operating Temp: 0°C to +50°C (32°F to 122°F)
Storage Temp: ‑40°C to +85°C (‑40°F to +185°F)
Humidity: 10%–90% RH, non‑condensing
Dimensions: 140 mm × 80 mm × 50 mm
Key Features
High‑Density RTD Input: 16 isolated channels for 3‑wire/4‑wire Pt100 sensors。
Full Isolation: Eliminates ground loops and crosstalk in noisy industrial environments。
High Precision: ±0.05% accuracy for critical temperature monitoring。
Solid‑State Design: No moving parts; conformal coated for dust/moisture resistance。
Sensor Fault Detection: Open/short‑circuit RTD detection (<1 second)。
Wide Compatibility: Works with standard Pt100 RTDs for diverse industrial applications。
Applications
Industries: Power generation, petrochemical, oil & gas, pulp & paper, pharmaceuticals, food & beverage。
System Role: Primary RTD input interface for Honeywell UCN/TDC3000 DCS。
Use Cases:
Precision temperature monitoring in reactors, furnaces, and pipelines。
High‑density RTD signal multiplexing in large process plants。
Accurate temperature control for critical manufacturing processes。
Installation & Wiring
ESD Precautions: Wear anti‑static wristbands and use ESD‑safe surfaces。
Power Off: De‑energize the I/O chassis/PM before insertion/removal。
Chassis Installation: Insert into a UCN I/O slot and secure with screws。
Field Wiring:
Connect RTD 3‑wire/4‑wire leads to compression terminals。
Use shielded twisted‑pair cable; maintain polarity and cable length consistency。
Configuration: Use Experion/TPS tools to set RTD type, range, and scaling parameters。
Maintenance
Periodic Inspection: Check LED status, terminal tightness, and 24 VDC power。
Cleaning: Remove dust with a dry, soft cloth; avoid liquids。
Fault Handling:
Verify RTD wire integrity and connection polarity。
Check for open/short circuits in field wiring。
Use system diagnostics to identify channel/board faults。
Safety Notes
Perform all work with chassis power disconnected。
Operate within rated temperature and humidity limits。
Unauthorized modification or disassembly is prohibited。
Comply with site ESD and safety procedures。
Get a Quote