The 51305890‑175 (also known as MC‑TAMT04) is a Low‑Level Multiplexer (LLMUX2) Thermocouple FTA (Field Termination Assembly) for Honeywell TDC3000 / TPS / Experion PKS DCS. It is designed for high‑accuracy temperature measurement, accepting millivolt‑level thermocouple signals, providing cold‑junction compensation (CJR), and delivering isolated, conditioned inputs to the control system.

Description

Product Overview

The 51305890‑175 (also known as MC‑TAMT04) is a Low‑Level Multiplexer (LLMUX2) Thermocouple FTA (Field Termination Assembly) for Honeywell TDC3000 / TPS / Experion PKS DCS. It is designed for high‑accuracy temperature measurement, accepting millivolt‑level thermocouple signals, providing cold‑junction compensation (CJR), and delivering isolated, conditioned inputs to the control system.

Basic Information

  • Part Number: 51305890175 (51305890‑175)

  • Alternate PN: MC‑TAMT04

  • Module Type: Low‑Level Analog Input Mux / Thermocouple FTA

  • Compatible Systems: Honeywell TDC3000, TPS, Experion PKS (UCN)

  • Manufacturer: Honeywell

  • Weight: Approx. 0.85 kg

  • Status: Discontinued (new/remanufactured/used available)

  • Certification: CE, UL, CSA

Technical Specifications

  • Input Channels: 16 fully isolated thermocouple inputs (expandable to 64 in 16‑ch increments)

  • Signal Type: Thermocouple (millivolt range: ±100 mV)

  • Isolation: 1500 VAC channel‑to‑channel, channel‑to‑PM, channel‑to‑supply

  • Cold Junction: Local/remote CJR support; fast open‑TC detection (<1 sec)

  • CMRR: 120 dB min (50/60 Hz, 1000 Ω source)

  • NMRR: 60 dB min (50/60 Hz)

  • Power: 24 VDC (15–30 VDC), 160 mA @ 15 VDC (from backplane/PMIO)

  • Operating Temp: 0°C to +50°C (32°F to 122°F)

  • Storage Temp: ‑40°C to +85°C (‑40°F to +185°F)

  • Humidity: 10%–90% RH, non‑condensing

  • Dimensions: 305 mm × 119 mm × 70 mm

Key Features

  1. High‑Density TC Input: 16 isolated channels per board; supports up to 64 channels total.

  2. Full Isolation: Eliminates ground loops and crosstalk in noisy industrial environments.

  3. Cold‑Junction Compensation: Ensures accurate temperature readings with local/remote CJR.

  4. Solid‑State Design: No mercury‑wetted relays; conformal coated for harsh conditions.

  5. Fast Fault Detection: Open thermocouple detection in <1 second.

  6. High Noise Immunity: 120 dB CMRR / 60 dB NMRR for stable low‑level signal capture.

Applications

  • Industries: Power generation, petrochemical, oil & gas, pulp & paper, metallurgy, pharmaceuticals.

  • System Role: Primary thermocouple input interface for Honeywell UCN/TDC3000 DCS.

  • Use Cases:

    • Precision temperature monitoring in reactors, furnaces, and turbines.

    • High‑density TC signal multiplexing in large process plants.

    • Cold‑junction compensated temperature data acquisition for control loops.

Installation & Wiring

  1. ESD Precautions: Wear anti‑static wristbands and use ESD‑safe surfaces.

  2. Power Off: De‑energize the I/O chassis/PM before insertion/removal.

  3. Chassis Installation: Insert into a UCN I/O slot and secure with screws.

  4. Field Wiring:

    • Connect thermocouple ± leads to compression terminals.

    • Use shielded twisted‑pair cable; maintain polarity and CJR wiring.

  5. Configuration: Use Experion/TPS tools to set TC type, range, and CJR parameters.

Maintenance

  • Periodic Inspection: Check LED status, terminal tightness, and 24 VDC power.

  • Cleaning: Remove dust with a dry, soft cloth; avoid liquids.

  • Fault Handling:

    • Verify TC wire integrity and polarity.

    • Check CJR sensor and wiring.

    • Use system diagnostics to identify channel/board faults.

Safety Notes

  • Perform all work with chassis power disconnected.

  • Operate within rated temperature and humidity limits.

  • Unauthorized modification or disassembly is prohibited.

  • Comply with site ESD and safety procedures.