51304754100
Description
Product Overview
Basic Information
Part Number: 51304754100
Model: MU‑PAIH03
Type: 16‑channel high‑level analog input processor
Compatible Systems: Experion PKS, C300, C200, TDC3000
Installation: Standard 19‑inch UCN I/O rack
Coating: Standard coating (non‑conformal)
Certifications: CE, RoHS, UL, EMC compliant
Technical Specifications
Input Channels: 16 differential analog inputs
Signal Type: Voltage (0–5 V, 1–5 V, 0.4–2 V), 4–20 mA (via 250 Ω resistor)
A/D Resolution: 16‑bit (14 bits used)
Accuracy: ±0.075% FSR (23.5°C ±2°C); ±0.15% FSR (0–50°C)
Common‑Mode Rejection: 70 dB (DC–60 Hz)
Normal‑Mode Rejection: 32 dB @ 60 Hz
Input Impedance: >10 MΩ (voltage inputs)
Scan Rate: 4 samples/channel/second (all channels within 250 ms)
Power Supply: 24 VDC backplane
Power Consumption: ≤12 W
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Key Features
16 differential channels for high‑density, high‑precision data acquisition.
Strong common‑mode rejection suppresses ground loops and noise.
Supports multiple voltage ranges and 4–20 mA transmitter inputs.
Hot‑swappable for online replacement without system shutdown.
LED indicators for power, run, fault, and channel status.
Standard coating for general industrial environments.
Typical Applications
Industries: Power, chemical, petroleum, water treatment, manufacturing.
Devices: Pressure/flow/temperature transmitters, level sensors, analog meters.
Installation & Wiring
Install in a standard UCN I/O rack; ensure proper grounding.
For voltage inputs: Use twisted‑pair shielded cable; connect shield to earth at one end.
For 4–20 mA: Add external 250 Ω resistor; wire per Honeywell guidelines.
Separate signal cables from high‑voltage lines; follow ESD precautions.
Indicators
PWR (Green): On when power is normal.
RUN (Green): Flashing during normal operation.
FLT (Red): On for module/channel fault or overrange.
Channel LEDs: On when input is within range; blink if overrange.
Maintenance & Safety
De‑energize the rack before installation or removal.
Inspect wiring and terminals periodically; keep module clean.
Do not disassemble; use only Honeywell original replacements.
Operate within rated temperature, voltage, and current limits.
Get a Quote