51304748125 (MU‑TAIX02) is an 8‑channel analog input FTA (Field Termination Assembly) for Honeywell Experion PKS, C300, C200, and TDC3000 DCS. It provides GI (General Instrument) isolation for standard industrial analog signal acquisition.

Description

Product Overview

51304748125 (MU‑TAIX02) is an 8‑channel analog input FTA (Field Termination Assembly) for Honeywell Experion PKS, C300, C200, and TDC3000 DCS. It provides GI (General Instrument) isolation for standard industrial analog signal acquisition.

Basic Information

  • Part Number: 51304748125

  • Model: MU‑TAIX02

  • Type: 8‑channel analog input FTA, GI isolation

  • Compatible Systems: Experion PKS, C300, C200, TDC3000

  • Installation: Standard 19‑inch UCN I/O rack

  • Coating: Standard coating (non‑conformal)

  • Certifications: CE, RoHS, UL, EMC compliant

Technical Specifications

  • Input Channels: 8 isolated analog inputs

  • Signal Type: 4–20 mA, 0–10 VDC (software configurable)

  • Isolation: Channel‑to‑chassis 500 Vrms galvanic isolation (GI)

  • Resolution: 16‑bit

  • Accuracy: ±0.1% FSR at 25 °C

  • Power Supply: 24 VDC backplane

  • Power Consumption: ≤10 W

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5%–95% RH, non‑condensing

Key Features

  1. Compact 8‑channel design saves rack space.

  2. GI isolation rejects common‑mode noise and ground loops.

  3. Hot‑swappable for online replacement without shutdown.

  4. LED indicators for power, run, fault, and channel status.

  5. Accepts 4–20 mA (transmitters) and 0–10 VDC signals.

  6. Standard coating for general industrial environments.

Typical Applications

  • Industries: Power, chemical, petroleum, water treatment, manufacturing.

  • Devices: Pressure/flow/temperature transmitters, level sensors, analog meters.

Installation & Wiring

  • Install in a standard UCN I/O rack; ensure proper grounding.

  • For 4–20 mA: Use twisted‑pair shielded cable; connect shield to earth at one end.

  • For 0–10 VDC: Use shielded cable; keep runs short.

  • Separate signal cables from high‑voltage lines; follow ESD precautions霍尼韦尔.

Indicators

  • PWR (Green): On when power is normal.

  • RUN (Green): Flashing during normal operation.

  • FLT (Red): On for module/channel fault or overrange.

  • Channel LEDs: On when input is within range; blink if overrange.

Maintenance & Safety

  • De‑energize the rack before installation or removal.

  • Inspect wiring and terminals periodically; keep module clean.

  • Do not disassemble; use only Honeywell original replacements.

  • Operate within rated temperature, voltage, and current limits霍尼韦尔