51304728375
May 22, 2026

51304728375

51304728375 (MU-GDID13) is a 32‑Channel Digital Input (DI) Field Termination Assembly (FTA) with galvanic isolation, designed for Honeywell Experion PKS / C300 / C200 DCS. It provides isolated 24 VDC digital input interfaces for discrete field devices, supporting redundant IOP and harsh‑environment conformal coating.

Description

1. Product Overview

51304728375 (MU-GDID13) is a 32‑Channel Digital Input (DI) Field Termination Assembly (FTA) with galvanic isolation, designed for Honeywell Experion PKS / C300 / C200 DCS. It provides isolated 24 VDC digital input interfaces for discrete field devices, supporting redundant IOP and harsh‑environment conformal coating.

2. Basic Information

  • Part Number: 51304728375 (51304728‑375)

  • Model: MU‑GDID13

  • Type: DI FTA, 32‑ch, 24 VDC, Galvanic Isolation, Redundant, Conformal Coating

  • Compatible Systems: Experion PKS, C300, C200, TDC3000

  • Mounting: Standard 19‑inch UCN I/O rack

  • Weight: Approx. 0.9 kg

  • Dimensions: 318 × 29 × 278 mm

3. Technical Specifications

  • Channels: 32 isolated digital inputs (2 × 16 groups)

  • Input Voltage: 24 VDC nominal (18–30 VDC operating)

  • Input Type: Dry contact, sink (NPN) / source (PNP) compatible

  • Input Current: 10 mA per channel @ 24 VDC

  • Isolation: 500 Vrms channel‑to‑chassis; 250 Vrms channel‑to‑channel (galvanic)

  • Response Time: ≤ 1 ms (ON/OFF)

  • Power Supply: 24 VDC from backplane

  • Power Consumption: ≤ 9 W

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5%–95% RH, non‑condensation

  • Coating: Conformal coating (G3 harsh environment)

  • Certifications: CE, RoHS, UL, EMC compliant

4. Key Features

  1. 32‑Channel High Density: Compact design saves cabinet space.

  2. Galvanic Isolation: 500 Vrms isolation eliminates ground loops and noise.

  3. Conformal Coating: Protects against humidity, dust, and corrosive gases.

  4. Redundant Support: Matches redundant DI IOP for high availability.

  5. Sink/Source Universal: Works with NPN/PNP sensors and dry contacts.

  6. Channel Diagnostics: Open/short‑circuit detection per channel.

  7. Hot Swappable: Replace without system shutdown.

  8. LED Status: Per‑channel and module health indicators.

5. Application Scope

Used in chemical, oil & gas, power generation, pharmaceutical, water treatment industries. Interfaces limit switches, pressure switches, level switches, relay contacts, and proximity sensors for DCS logic/sequential control.

6. Installation Instructions

  1. Power Off: Disconnect rack power before installation/removal.

  2. Rack Insertion: Slide into UCN slot; secure with front screws.

  3. Field Wiring: Use shielded twisted‑pair (22–24 AWG) per channel.

  4. Cable Separation: Keep signal cables ≥ 30 cm from high‑voltage lines.

  5. Shield Grounding: Single‑point ground at FTA end to avoid loops.

  6. ESD Protection: Wear anti‑static gloves/wrist strap during handling.

7. LED Indicator Description

  • PWR (Green): On = 24 VDC power normal.

  • RUN (Green): Flashing = Active IOP communication.

  • FLT (Red): On = Module fault; Flashing = Channel fault.

  • CH01–CH32 (Yellow): On = Input ON; Off = Input OFF.

8. Maintenance

  1. Monthly Inspection: Check wiring tightness and LED status.

  2. Cleaning: Use dry lint‑free cloth only; no liquids/abrasives.

  3. Fault Handling: If FLT is on, check wiring/field devices; replace FTA if needed.

  4. Spare Parts: Use only original Honeywell 51304728375 units.

9. Safety Precautions

  1. Power‑Only Work: Wiring/maintenance must be done with rack power off.

  2. Environmental Limits: Do not exceed rated temperature/voltage/humidity.

  3. No Modification: Do not open or modify internal components; voids warranty.

  4. Hazardous Areas: For IS use, follow approved wiring and barrier standards。


Get a Quote