51304718200
Description
1. Product Overview
2. Part Number & Physical Details
Part Number: 51304718200 (51304718‑200)
Module Type: High Level Analog Input (UCN)
Applicable Systems: Honeywell TDC3000, Experion PKS, UCN DCS
Dimensions: 318 × 29 × 278 mm
Weight: Approx. 0.9–1.0 kg
Mounting: Standard UCN/APM rack slot
3. Technical Specifications
Input Channels: 16 isolated analog inputs
Signal Types (per channel, configurable):
Current: 4–20 mA (250 Ω shunt optional)
Voltage: 0–10 V, ±5 V, ±10 V
Isolation: Enhanced point‑to‑chassis, point‑to‑point galvanic isolation (250 Vrms)
Resolution: 16‑bit
Accuracy: ±0.05% FS (25 °C) (best‑in‑class for the series)
Power Supply: 24 VDC (backplane‑fed)
Power Consumption: ≤ 10 W
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Humidity: 5–95% RH, non‑condensing
Certifications: CE, RoHS, UL, Honeywell EMC compliant
Coating: Conformal coated PCB for harsh environments
Diagnostics: Channel‑level fault detection (open/short circuit, overrange)
4. Key Features
16‑Channel Enhanced Isolation: Each channel is galvanically isolated from chassis and other channels, eliminating ground loops and protecting against common‑mode voltage.
Software‑Configurable Ranges: Select mA/V ranges via Honeywell Process Control Designer (no hardware jumpers).
High Noise Rejection: Upgraded EMI/RFI filtering for high‑noise industrial plants (power, chemical, oil & gas).
Hot‑Swappable: Online replacement without system shutdown (minimizes downtime).
Advanced LED Status Indicators:
PWR (Green): Steady = power normal; Flashing = power fault
RUN (Green): Flashing = module active; Steady = fault
FLT (Red): On = channel fault; Flashing = critical module error
Channel‑Level Diagnostics: Detects open/short circuits, overrange, and sensor faults for quick troubleshooting.
5. Application Range
Target Systems: Honeywell TDC3000, Experion PKS, UCN DCS
Industries: Power generation, chemical, oil & gas, refining, water treatment, pharmaceuticals
Function: Monitor transmitters (pressure, flow, level, temperature) via 4–20 mA/0–10 V signals; ideal for critical control loops requiring high accuracy and reliability.
6. Installation Instructions
ESD Protection: Wear anti‑static gloves/wristband before handling.
Power Off: Power off the rack before insertion/removal.
Insertion: Insert into standard UCN slot and secure with screws.
Wiring: Use shielded twisted‑pair (STP) cable for field inputs (18–22 AWG).
Cable Routing: Route cables away from high‑voltage lines (≥ 30 cm separation).
Grounding: Ground shields at one end only (control room side) to avoid ground loops.
7. Maintenance Notes
Quarterly Inspection: Check connections for tightness; clean with dry cloth only.
Cleaning: Avoid harsh solvents (use isopropyl alcohol only if necessary).
Spare Parts: Use only genuine Honeywell spares for replacement.
Fault Troubleshooting (FLT LED On):
Check field wiring for open/short circuits.
Verify input range matches transmitter output.
Check shunt resistor (250 Ω) for 4–20 mA signals.
Replace module if fault persists.
8. Safety Requirements
Power Off: All wiring/maintenance must be done with power off.
Voltage Rating: Do not exceed 30 VDC on input channels.
Temperature: Do not operate above +60 °C or below 0 °C.
No Disassembly: Do not open or modify the module (voids warranty).
ESD Protection: Handle only in ESD‑protected areas.
Get a Quote