51304718125
May 22, 2026

51304718125

51304718125 (51304718-125) is a 16‑channel high‑level analog input module for Honeywell TDC3000 / UCN DCS systems. It monitors process variables (pressure, flow, temperature) via 4–20 mA or 0–10 V signals, with galvanic isolation for noise immunity and safety.

Description

1. Product Overview

51304718125 (51304718-125) is a 16‑channel high‑level analog input module for Honeywell TDC3000 / UCN DCS systems. It monitors process variables (pressure, flow, temperature) via 4–20 mA or 0–10 V signals, with galvanic isolation for noise immunity and safety.

2. Part Number & Physical Details

  • Part Number: 51304718125 (51304718‑125)

  • Module Type: High Level Analog Input (UCN)

  • Applicable Systems: Honeywell TDC3000, Experion PKS, UCN DCS

  • Dimensions: 318 × 29 × 278 mm

  • Weight: Approx. 0.9–1.0 kg

  • Mounting: Standard UCN/APM rack slot

3. Technical Specifications

  • Input Channels: 16 isolated analog inputs

  • Signal Types (per channel, configurable):

    • Current: 4–20 mA (250 Ω shunt optional)

    • Voltage: 0–10 V, ±5 V, ±10 V

  • Isolation: Point‑to‑chassis, point‑to‑point galvanic isolation

  • Resolution: 16‑bit

  • Accuracy: ±0.1% FS (25 °C)

  • Power Supply: 24 VDC (backplane‑fed)

  • Power Consumption: ≤ 10 W

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5–95% RH, non‑condensing

  • Certifications: CE, RoHS, UL, Honeywell EMC compliant

  • Coating: Conformal coated PCB for harsh environments

4. Key Features

  1. 16‑Channel Isolation: Each channel is galvanically isolated from chassis and other channels.

  2. Dual‑Range Config: Software‑selectable mA/V ranges via Honeywell Process Control Designer.

  3. High Noise Rejection: Isolation eliminates ground loops and electrical interference.

  4. Hot‑Swappable: Online replacement without system shutdown.

  5. LED Status Indicators:

    • PWR (Green): Steady = power normal

    • RUN (Green): Flashing = module active

    • FLT (Red): On = input fault/diagnostic error

5. Application Range

  • Target Systems: Honeywell TDC3000, Experion PKS, UCN DCS

  • Industries: Power, chemical, oil & gas, refining, water treatment.

  • Function: Monitor transmitters (pressure, flow, level, temperature) via 4–20 mA/0–10 V.

6. Installation Instructions

  1. Power off the rack before insertion/removal.

  2. Insert into standard UCN slot and secure.

  3. Use shielded twisted‑pair cable for field inputs.

  4. Route cables away from high‑voltage lines.

  5. Ground shields at one end only to avoid loops.

7. Maintenance Notes

  • Inspect connections quarterly; clean with dry cloth only.

  • Avoid harsh solvents; use only genuine Honeywell spares.

  • If FLT LED is on, check field wiring, input range, and shunt resistors.

8. Safety Requirements

  • All wiring/maintenance must be done with power off.

  • Do not exceed rated voltage/temperature.

  • Do not disassemble the module.


Get a Quote