51304718125
Description
1. Product Overview
2. Part Number & Physical Details
Part Number: 51304718125 (51304718‑125)
Module Type: High Level Analog Input (UCN)
Applicable Systems: Honeywell TDC3000, Experion PKS, UCN DCS
Dimensions: 318 × 29 × 278 mm
Weight: Approx. 0.9–1.0 kg
Mounting: Standard UCN/APM rack slot
3. Technical Specifications
Input Channels: 16 isolated analog inputs
Signal Types (per channel, configurable):
Current: 4–20 mA (250 Ω shunt optional)
Voltage: 0–10 V, ±5 V, ±10 V
Isolation: Point‑to‑chassis, point‑to‑point galvanic isolation
Resolution: 16‑bit
Accuracy: ±0.1% FS (25 °C)
Power Supply: 24 VDC (backplane‑fed)
Power Consumption: ≤ 10 W
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Humidity: 5–95% RH, non‑condensing
Certifications: CE, RoHS, UL, Honeywell EMC compliant
Coating: Conformal coated PCB for harsh environments
4. Key Features
16‑Channel Isolation: Each channel is galvanically isolated from chassis and other channels.
Dual‑Range Config: Software‑selectable mA/V ranges via Honeywell Process Control Designer.
High Noise Rejection: Isolation eliminates ground loops and electrical interference.
Hot‑Swappable: Online replacement without system shutdown.
LED Status Indicators:
PWR (Green): Steady = power normal
RUN (Green): Flashing = module active
FLT (Red): On = input fault/diagnostic error
5. Application Range
Target Systems: Honeywell TDC3000, Experion PKS, UCN DCS
Industries: Power, chemical, oil & gas, refining, water treatment.
Function: Monitor transmitters (pressure, flow, level, temperature) via 4–20 mA/0–10 V.
6. Installation Instructions
Power off the rack before insertion/removal.
Insert into standard UCN slot and secure.
Use shielded twisted‑pair cable for field inputs.
Route cables away from high‑voltage lines.
Ground shields at one end only to avoid loops.
7. Maintenance Notes
Inspect connections quarterly; clean with dry cloth only.
Avoid harsh solvents; use only genuine Honeywell spares.
If FLT LED is on, check field wiring, input range, and shunt resistors.
8. Safety Requirements
All wiring/maintenance must be done with power off.
Do not exceed rated voltage/temperature.
Do not disassemble the module.
Get a Quote