51304690100
Description
1. Product Overview
2. Part Number & Physical Details
Part Number: 51304690100 (51304690‑100)
Module Type: Digital Input SOE Card (TDC3000/UCN)
Applicable Systems: Honeywell TDC3000, UCN DCS
Dimensions: 318 × 29 × 278 mm
Weight: Approx. 0.59–1.0 kg
Mounting: Standard UCN/APM rack slot
3. Technical Specifications
Input Voltage: 24 VDC (field‑side)
Input Channels: 16 isolated digital inputs
SOE Resolution: 1 ms (high‑resolution timestamping)
Filtering: Each channel has noise filtering to prevent false triggering
Isolation: Channel‑to‑backplane isolation
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Humidity: 0–95% RH, non‑condensing
Certifications: CE, RoHS, UL, Honeywell EMC compliant
Coating: Conformal coated PCB for harsh environments
4. Key Features
SOE Sequence Recording: Captures precise 1 ms timestamps for all input transitions.
High Noise Immunity: Per‑channel filtering rejects electrical interference.
16 Isolated Inputs: Monitors discrete devices (switches, interlocks, relays).
Industrial Hardening: Conformal coating protects against dust, moisture, and contaminants.
LED Status Indicators:
PWR (Green): Steady = power OK
RUN (Green): Flashing = module active
FLT (Red): On = input fault or diagnostic error
Hot‑Swappable: Online replacement without system shutdown.
5. Application Range
Target Systems: Honeywell TDC3000, UCN DCS
Industries: Power, chemical, oil & gas, refining, water treatment.
Function: SOE event logging, critical contact monitoring, trip analysis.
6. Installation Instructions
Power off the rack before insertion/removal.
Insert into standard UCN slot and secure.
Use twisted‑pair shielded cable for field inputs.
Route cables away from high‑voltage lines.
Ground shields at one end only to avoid loops.
7. Maintenance Notes
Inspect connections quarterly; clean with dry cloth only.
Avoid harsh solvents; use only genuine Honeywell spares.
If FLT LED is on, check field wiring and input voltage.
8. Safety Requirements
All wiring/maintenance must be done with power off.
Do not exceed rated voltage/temperature.
Do not disassemble the module.
Get a Quote