51304685250
Description
1. Product Overview
2. Part Number & Physical Details
Part Number: 51304685250 (51304685-250)
Module Type: Advanced Communication Module (APMM), R300 (AdvCommR300)
Applicable Systems: Honeywell Experion PKS, TDC3000, UCN DCS
Dimensions: 318 × 29 × 278 mm (same as R200 series)
Weight: Approx. 0.95–1.0 kg
Mounting: Standard Honeywell UCN/APM rack slot
3. Technical Specifications
Power Supply: 24 VDC (backplane-fed)
Power Consumption: ≤ 8 W
Network Architecture: UCN (Universal Control Network)
Communication Speed: Up to 75 Mbps (UCN)
Ethernet Ports: 2 × 10/100 Mbps (copper; fiber optional)
Max Nodes: Up to 16 UCN devices per module
Supported Protocols: UCN proprietary protocol, Ethernet/IP, Modbus TCP
Isolation: Port-to-port, channel-to-backplane isolation
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Certifications: CE, RoHS, UL, Honeywell EMC compliant
4. Key Features (R300 Enhancements)
R300 Firmware Upgrade: Improved UCN routing, higher data throughput, and lower latency vs. R200/R210.
High-Speed UCN Communication: Real-time, reliable data exchange for critical process control.
1:1 Redundancy Support: Eliminates single points of failure; seamless failover.
Precision Time Synchronization: Millisecond-level timestamping for distributed control and event logging.
Hot-Swappable Design: Online replacement without system shutdown.
Conformal Coating: Dust/moisture protection for harsh industrial environments.
LED Status Indicators:
PWR (Green): Steady = power normal
RUN (Green): Flashing = module operating normally
FLT (Red): On = communication fault or error
5. Application Range
Target Systems: Honeywell Experion PKS, TDC3000, UCN DCS
Industries: Power generation, chemical, petroleum refining, water treatment, and other process industries.
Function: Central communication hub for controllers, I/O, and HMI/SCADA layers.
6. Compatibility Notes
Backward Compatible: Works with existing UCN racks and R200-series modules.
Replacement: Direct upgrade for 51304685200 (R210) or 51304685150 (R400) in the same slot.
7. Installation & Maintenance
Installation: Power off rack → insert into standard slot → secure → connect shielded Ethernet cables.
Maintenance: Periodic connection inspection; clean with dry cloth only; use genuine Honeywell parts.
8. Safety Requirements
Power off before wiring/maintenance.
Do not exceed rated temperature/voltage.
Do not disassemble internal components.
Get a Quote