51304672150
May 22, 2026

51304672150

51304672150 (51304672-150) is an 8‑channel isolated analog output module for Honeywell DCS (e.g., Experion, TDC3000/UCN) systems. It converts digital control signals into precision 4–20 mA / 0–10 V analog outputs for valves, actuators, and transmitters.

Description

1. Product Overview

51304672150 (51304672-150) is an 8‑channel isolated analog output module for Honeywell DCS (e.g., Experion, TDC3000/UCN) systems. It converts digital control signals into precision 4–20 mA / 0–10 V analog outputs for valves, actuators, and transmitters.

2. Part Number & Revision

  • Model: 51304672150 (51304672-150)

  • Assy No: 51304672-150

  • Hardware: Rev J

  • Firmware: Rev D

  • Weight: approx. 310 g

  • Dimensions: 142 × 71 × 25 mm

3. Technical Specifications

  • Channels: 8 isolated analog outputs

  • Output Signals:

    • Current: 4–20 mA (sink/source)

    • Voltage: 0–10 VDC

  • Accuracy: ±0.1% FS @ 25 °C

  • Resolution: 16‑bit

  • Load Limits:

    • Current: ≤ 600 Ω

    • Voltage: ≥ 1 kΩ

  • Isolation: Channel‑to‑channel & channel‑to‑bus

  • Power: 24 VDC (backplane‑supplied)

  • Operating Temp: 0 °C to +60 °C

  • Storage Temp: −40 °C to +85 °C

  • Certifications: CE, RoHS, UL

4. Key Features

  • 8‑channel high‑precision analog output

  • Per‑channel short‑circuit & overload protection

  • LED status indicators (PWR/RUN/FLT)

  • Hot‑swappable (no system shutdown required)

  • Redundancy‑capable for high‑availability systems

  • DIN‑rail / rack‑mount compatible

5. Applications

  • Honeywell DCS/Experion process control

  • Chemical, petrochemical, power, water treatment

  • Industrial automation: valves, actuators, motor drives

  • Building HVAC & facility management

6. Installation & Wiring

  1. Power Off: Disconnect system power before installation.

  2. Rack Insertion: Slide module into designated I/O rack slot; secure latch.

  3. Field Wiring:

    • Use shielded twisted‑pair (STP) (22–18 AWG).

    • Ground shield only at control room end to avoid ground loops.

    • Terminate per channel: +/− for current/voltage.

  4. Separation: Keep analog cables ≥ 30 cm from high‑voltage AC lines.

7. LED Indicator Description

  • PWR (Green): On = 24 VDC power normal

  • RUN (Green): Flashing = normal operation

  • FLT (Red): On = fault (short, overload, communication error)

8. Maintenance & Troubleshooting

  • Inspect: Check connectors, physical damage, corrosion quarterly.

  • Clean: Use dry cloth only; no liquid cleaners.

  • Fault Handling:

    • If FLT is on: Check field wiring for shorts/overloads.

    • Verify backplane power and rack communication.

  • Replacement: Use only Honeywell original modules; power off before removal.

9. Safety Precautions

  • Electrical: Disconnect all power before wiring/maintenance.

  • Environmental: Avoid moisture, dust, corrosive gases beyond ratings.

  • Modification: Do not alter hardware/firmware; use OEM replacements.

10. Ordering Information

  • Part Number: 51304672150 (51304672-150)

  • Description: Honeywell 8‑Channel Analog Output Module, Rev J/D

  • Compatible Systems: Honeywell Experion, TDC3000, UCN I/O Racks


Get a Quote