IC698RMX016 VMIVME-5567-100
May 11, 2026

IC698RMX016 VMIVME-5567-100

1. Product Overview The IC698RMX016 (VMIVME-5567-100) is a redundant memory xchange module designed for the Emerson (GE Fanuc) PACSystems RX7i control system. It enables high-speed, deterministic data sharing between multiple RX7i controllers using reflective memory technology, supporting real-time redundancy and data synchronization for mission-critical applications.

Description


1. Product Overview

The IC698RMX016 (VMIVME-5567-100) is a redundant memory xchange module designed for the Emerson (GE Fanuc) PACSystems RX7i control system. It enables high-speed, deterministic data sharing between multiple RX7i controllers using reflective memory technology, supporting real-time redundancy and data synchronization for mission-critical applications.
image

2. Key Features

  • Reflective Memory Technology: Real-time data mirroring across up to 256 nodes

  • Fiber Optic Interface: 2 × LC-type fiber ports (62.5/125 μm multimode)

  • Data Transfer Rate: 2.12 Gbaud (fiber), up to 200 MB/s (payload)

  • Memory Size: 16 MB shared memory space

  • Redundancy Support: Dual-module redundancy (primary/backup)

  • VMEbus Compatibility: VME64x standard, single-slot form factor

  • Protocols: Reflective Memory Protocol (RMP), supports GE 5565-series devices

  • Interrupt Support: VME interrupts for event-driven data exchange

  • Diagnostics: On-board LED indicators, parity error detection


3. Technical Specifications

3.1 Electrical

ParameterValue
Backplane Power+5 VDC @ 1.2 A; ±12 VDC @ 0.1 A
Power Consumption6 W (typical)
Isolation1500 VDC (fiber-to-backplane)

3.2 Communication

ParameterValue
Fiber Ports2 × LC (multimode, 62.5 μm core)
Fiber DistanceUp to 300 m (62.5 μm multimode)
Data Rate2.12 Gbaud (fiber), 200 MB/s (max payload)
Network NodesUp to 256 (compatible with 5565-series)
Shared Memory16 MB (global address space)
Access Time200–400 ns

3.3 Environmental

ParameterValue
Operating Temperature0 °C to +60 °C (free cooling)
Storage Temperature–40 °C to +85 °C
Humidity5–95% non-condensing
Altitude≤2000 m
Shock/VibrationIEC 60068-2-6 compliant

3.4 Mechanical

ParameterValue
Form FactorSingle-slot VME64x, RX7i rack mount
Dimensions (H×W×D)170 × 150 × 30 mm
Weight~1.2 kg
MountingRX7i main rack (Slot 3/4 recommended)

4. Panel Indicators & Controls

4.1 Front Panel LEDs

LEDStateMeaning
PWR (Green)SolidBackplane power OK

OffNo power or fault
LINK (Green)SolidFiber link active

BlinkingData activity

OffNo fiber connection
FAULT (Red)SolidParity error / hardware fault

BlinkingNetwork timeout / sync loss

OffNormal operation

4.2 Controls

  • Reset Button: Momentary press to reset module (preserves memory data)

  • Fiber Ports: 2 × LC connectors (PORT1/PORT2) for network connection


5. Installation

5.1 Pre-Installation

  1. Disconnect all power from the RX7i rack.

  2. Select target slot (Slot 3 or 4 recommended for interrupt priority).

  3. Verify backplane is undamaged and slot is empty.

5.2 Rack Installation

  1. Align module with selected RX7i rack slot.

  2. Insert firmly until backplane connector is fully seated.

  3. Secure module with front-panel screws (torque 0.8–1.0 N·m).

  4. Connect fiber cables to LC ports (PORT1/PORT2).

  5. Restore power; verify PWR LED illuminates.

5.3 Network Wiring

  • Topology: Daisy-chain or star (using fiber switch)

  • Cable: 62.5/125 μm multimode fiber, LC connectors

  • Termination: No external termination required (internal termination)


6. Configuration

6.1 Software Setup

  • Use Proficy Machine Edition Logic Developer – PLC v4.0+

  • Configure as IC698RMX016 in RX7i project

6.2 Key Configuration Parameters

  1. Node ID: Unique 0–255 identifier (network-wide)

  2. Memory Offset: 0–16 MB (shared memory address)

  3. Redundancy Mode: Primary/Backup or Dual Primary

  4. Interrupt Enable: VME IRQ 1–7 (event notification)

  5. Parity Check: Enable/disable error detection

6.3 Configuration Steps

  1. In Machine Edition, navigate to I/O Configuration → RMX Module.

  2. Set Node ID and Memory Offset.

  3. Enable Redundancy Mode (if applicable).

  4. Download configuration to CPU.

  5. Power-cycle module to apply settings.


7. Operation

7.1 Power-On Sequence

  1. Apply power to RX7i rack; PWR LED lights.

  2. Module initializes; FAULT LED blinks during self-test.

  3. On successful test, FAULT LED off; LINK LED lights (fiber connected).

  4. CPU configures module; shared memory becomes available.

7.2 Normal Operation

  • Data Mirroring: Writes to local memory auto-broadcast to all network nodes

  • Real-Time Sync: Deterministic data update (<1 μs latency)

  • Redundancy: Backup module auto-takes over if primary fails

  • Interrupts: Triggers VME interrupt on data update (configurable)

7.3 Fault Handling

  • Fiber Link Loss: LINK LED off; module retries connection

  • Parity Error: FAULT LED on; logs error to CPU

  • Network Timeout: FAULT LED blinks; resets after timeout

  • Over-temperature: Reduces data rate; shuts down at >70 °C


8. Maintenance & Troubleshooting

8.1 Preventive Maintenance

  • Monthly: Inspect LED status; clean fiber ports (lint-free cloth)

  • Quarterly: Tighten module screws; check fiber cable integrity

  • Annual: Verify memory data integrity; update firmware (if available)

8.2 Troubleshooting

表格
SymptomPossible CauseSolution
PWR LED OffNo backplane power; faulty PSUCheck RX7i power supply; reseat module
LINK LED OffFiber cable fault; wrong portReplace cable; verify PORT1/PORT2 connection
FAULT LED OnParity error; bad memoryReset module; check configuration
Data Not SyncingWrong Node ID; memory offset conflictVerify Node ID; check memory range
Interrupts Not TriggeringIRQ disabled; wrong priorityEnable interrupts; check VME IRQ settings

9. Safety Precautions

  • Optical Safety: Fiber ports emit laser light; do not look into ports

  • Electrical Hazard: Backplane voltage can be lethal; disconnect power before servicing

  • ESD Protection: Use anti-static wristband when handling module

  • Temperature: Do not operate outside 0–60 °C; ensure adequate ventilation

  • EMI Compliance: Install in conductive metal enclosure for radiation compliance


10. Warranty & Support

  • Warranty: 12 months from delivery (defects in materials and workmanship)

  • Support: Contact Emerson Automation Solutions for technical assistance, repairs, or firmware updates


Get a Quote