0-50004-R
Description
Basic Information
Manufacturer: Reliance Electric (Rockwell Automation)
Part Number: 0-50004-R (alternate: 050004R)
Type: DC Amplifier Card (直流放大卡)
Series: SealPak (密封式直流驱动控制系统)
Function: High-gain DC signal amplification, power drive for control loops
Status: Obsolete / Discontinued (repair & surplus only)
NSN: 5996-00-827-3660
Electrical Specifications
Control Power: ±15 VDC (SealPak bus), +5 VDC logic
Input Signal: ±10 VDC (low-level analog)
Output Signal: ±10 VDC (high-current drive, up to 200 mA)
Gain Range: 10–1000 (adjustable via front pot)
Bandwidth: DC to 15 kHz
Accuracy: ±0.1% FSR
Protection: Short-circuit, overcurrent, thermal shutdown
Isolation: Galvanic isolation (I/O ↔ logic ground)
Mechanical & Environmental
Mounting: Standard SealPak slot-mount (slide-in + front lock screw)
Dimensions (L×W×H): 279 × 216 × 178 mm
Weight: Approx. 1.4 kg (3.0 lbs)
Operating Temp: 0°C to 55°C (32°F to 131°F)
Storage Temp: -25°C to 65°C (-13°F to 149°F)
Humidity: 5%–95% non-condensing
Coating: Conformal coated PCB (dust/moisture resistance)
Key Features
High-Gain DC Amplification: Precision gain for low-level signal boosting
Front-Panel Adjustment: Gain potentiometer; LED status (Power, Fault)
Heavy-Duty Output: Drives multiple control cards or power stages directly
Fault Protection: Self-protects against short circuits and overloads
Harsh Environment Ready: Sealed design for industrial floor use
Compatible Systems & Replacement
System: SealPak DC drive racks (legacy, paired with 0-50001-2R control card)
Matched Modules: 0-50001-2R (control), 0-50005 (I/O), 0-50010 (power)
Replacement: Direct replacement for older SealPak 0-50004 (non-R version)
Installation & Calibration
Installation
Power off the SealPak rack.
Insert 0-50004-R into an empty slot; tighten front locking screw.
Verify ±15 VDC and +5 VDC bus power.
Calibration
Power on; confirm Power LED is ON.
Apply a known ±10 VDC input signal.
Adjust Gain pot to get the desired output amplitude.
Check output current (≤200 mA) for stability.
Lock potentiometer; test under load.
Operation & Faults
Normal: Power LED ON; stable output; no fault triggers.
Fault LED ON: Short circuit, overcurrent, or thermal trip (reset after clearing fault).
No Output: Check bus power, wiring, on-board fuse, or input signal.
Get a Quote