3007-403-4-00
Description



3007-403-4-00
SEW MOVITRAC Frequency Inverter English Detailed Specification
1. Model Code Explanation
2. Core Electrical Parameters
Rated Power: 22 kW
Input Voltage: 3-phase AC 200V ~ 240V (Nominal 230V)
Input Frequency: 50 Hz / 60 Hz
Rated Output Current: 85 A
Output Voltage: 0 ~ 230 V three-phase AC
Output Frequency Range: 0 ~ 400 Hz
Control Mode: V/F open-loop control
Overload Capability: 150% rated current for 60 seconds
Switching Frequency: Adjustable range
3. Environmental & Physical Characteristics
Protection Degree: IP20
Cooling Method: Built-in fan forced air cooling
Working Ambient Temperature: 0 °C ~ +45 °C
Storage Temperature: -25 °C ~ +70 °C
Working Humidity: 5% ~ 95%, non-condensing
Installation Way: Vertical wall-mounted installation
Applicable Altitude: ≤1000 meters without power derating
4. Built-in Control Interfaces
Standard RS485 communication interface
Multi-group digital input and relay output terminals
0-10V analog frequency setting input port
Multi-section fixed speed control terminals
PTC motor over-temperature protection interface
External braking resistor matching interface
5. Main Operation Functions
Freely adjustable acceleration and deceleration time
Integrated dynamic braking unit for rapid stop
Intelligent energy-saving running mode
Support three control modes: local panel, external terminal and remote communication
Speed slip compensation function to ensure stable operation speed
Soft start and soft stop function to reduce mechanical impact
Built-in PID constant speed and constant pressure control function
6. Full Safety Protection Functions
Over current protection
Over voltage and under voltage protection
Input phase loss protection
Inverter internal over temperature protection
Motor overload electronic thermal protection
Output short circuit protection
Earth fault protection
Running stall prevention protection
7. Installation & Wiring Rules
Disconnect all power supply before wiring and maintenance operations
Power cables and control signal cables must be laid separately
Firmly connect reliable PE protective grounding wire
Reserve enough surrounding space for ventilation and heat dissipation
Do not install in dusty, humid, corrosive and strong vibration sites
Recommended to use shielded special motor cables for output wiring
8. Commissioning Operation Steps
Check all wiring to exclude wrong connection and short circuit risks
Confirm the input power voltage is consistent with inverter rated voltage
Set motor rated voltage, rated current and limit frequency parameters
Select matching control mode according to actual working demands
Perform no-load trial operation firstly and check running status
Put into formal load operation after stable no-load operation
9. Daily Maintenance Guidelines
Regularly clean cooling fan and internal accumulated dust
Periodically check the tightness of all wiring terminals
Real-time monitor operating current and internal working temperature
Replace aging or damaged cooling fans in time
All fault inspection and repair work must be operated by qualified professional electricians