3004-403-4-00
Description

3004-403-4-00
SEW MOVITRAC Frequency Inverter Detailed English Specification
1. Model Code Explanation
2. Electrical Specifications
Rated Power: 11 kW
Input Voltage: 3-phase AC 200~240 V (Nominal 230 V)
Input Frequency: 50 / 60 Hz
Rated Output Current: 42.0 A
Output Voltage: 0 ~ 230 V 3-phase AC
Output Frequency Range: 0 ~ 400 Hz
Control Mode: V/F open-loop control
Overload Capacity: 150% rated current for 60 seconds
Switching Frequency: Adjustable
3. Physical & Environmental Parameters
Protection Class: IP20
Cooling Method: Forced air cooling
Operating Temperature: 0 °C ~ +45 °C
Storage Temperature: -25 °C ~ +70 °C
Relative Humidity: 5%~95%, non-condensing
Installation: Vertical wall mounting
Altitude: ≤1000m no power derating
4. Standard Interfaces
Built-in RS485 communication port
Multi-channel digital input & relay output terminals
0-10V analog speed reference input
Multi-step speed control function terminals
Motor thermal protection signal interface
5. Main Functions
Adjustable acceleration & deceleration time
Integrated dynamic braking function for rapid stop
Energy saving operation mode
Local panel / external terminal / remote communication triple control
Slip compensation for stable speed operation
Soft start & soft stop to reduce mechanical impact
Automatic voltage regulation function
6. Complete Protection Functions
Over current protection
Over voltage & under voltage protection
Input phase loss protection
Inverter over temperature protection
Motor overload electronic thermal protection
Output short circuit protection
Earth fault protection
Stall prevention protection
7. Installation & Wiring Requirements
Disconnect all power before wiring and maintenance
Separate power cables and control cables to avoid interference
Ensure reliable PE protective grounding connection
Keep sufficient ventilation space for heat dissipation
Do not install in dusty, humid, corrosive and high-vibration areas
Adopt shielded dedicated motor cables for output wiring
8. Commissioning Procedures
Inspect all wiring to eliminate wrong connection and short circuit
Confirm input power voltage matches inverter rated specification
Set motor rated voltage, rated current and frequency limit parameters
Select suitable control mode according to actual working condition
Perform no-load test run and check operation status
Gradually load and put into formal operation after normal trial run
9. Daily Maintenance
Regularly clean cooling fan and internal dust
Periodically check tightness of all wiring terminals
Monitor running current and working temperature in real time
Replace damaged cooling fans timely
Only qualified professional electricians can conduct fault repair