IS215UCVFH2BB VMIVME-7650-83H 350-007650-83H C
April 24, 2026

IS215UCVFH2BB VMIVME-7650-83H 350-007650-83H C

IS215UCVFH2BB (VMIVME-7650-83H) is a VME main control board for GE Mark VI. With embedded CPU and TMR redundancy, it performs unit control operation, data exchange and communication for power plant turbine systems.

Description

1. Basic Information

  • Model Identifiers: IS215UCVFH2BB (GE System Model), VMIVME-7650-83H (VMIC OEM Model), 350-007650-83H C (Part Number)

  • Brand/Series: General Electric (GE) Speedtronic Mark VI Gas/Steam Turbine Control System, IS215 Series VME Bus Single-Board Computer (SBC), originally designed and manufactured by VMIC

  • Core Position: Main control/communication/HMI unit for Mark VI systems, responsible for turbine control algorithm execution, real-time data processing, system networking, and local monitoring, serving as the core computing and communication node.

2. Core Hardware Specifications

  • Processor: Intel Celeron or Pentium III (configurable), industrial-grade embedded CPU for real-time control computing.

  • Bus Architecture: 6U VME bus, single-slot mounting, compatible with Mark VI standard VME chassis, supports TMR (Triple Modular Redundancy) architecture.

  • Memory/Storage: 32MB DRAM, 16MB CompactFlash, 128KB L2 cache, battery-backed SRAM (data retention on power loss).

  • Power Supply: +5VDC (6.6A typical, 8.6A max), ±12VDC (180mA typical, 250mA max each), powered via VME backplane.

  • Operating Environment: 0°C to +55°C, industrial-grade, vibration and EMI resistant, suitable for power plant field conditions.

  • Form Factor: 6U VME single-slot board, standard embedded rack mounting.

3. Interfaces & Communication

  • Ethernet: Dual 10/100BaseTX (RJ45), supports GE IONet, Modbus, EGD protocols for redundant networking, remote monitoring and DCS integration.

  • Serial Ports: 2×RS-232C (9-pin micro D-sub), for commissioning, local device communication and configuration.

  • Display/Peripherals: VGA video output, keyboard/mouse interfaces for direct local terminal connection.

  • Status Indicators: LED run/fault indicators, reset button for easy installation, commissioning and fault diagnosis.

4. Core Functions & Applications

  • Executes core control logic and real-time computation for turbine speed regulation, protection, load control and sequence control, processing complex control algorithms.

  • Manages internal data exchange, I/O acquisition, redundant voting, fault diagnosis and switchover in Mark VI systems to ensure high reliability.

  • Supports program download, online monitoring, parameter tuning and system configuration; compatible with TMR architecture for critical power generation control.

  • Applications: GE Mark VI control systems for gas turbines, steam turbines, combined-cycle power plants and industrial power units, used for main control upgrades, spare parts replacement and system maintenance.


Get a Quote