Honeywell 51204160175 (51204160-175) Product Details
Description

Honeywell 51204160175 (51204160-175) Product Details
Model: 51204160175 (Standard Number: 51204160-175)
Brand: Honeywell
Model Alias: MC-TAIY62
Product Type: 32-channel 4-20mA Analog Input FTA Terminal Board (AI FTA)
Compatible Systems: TDC 3000 / TPS / Experion PKS UCN System
I. Product Overview
51204160-175 (MC-TAIY62) is a 32-channel analog output field terminal component of Honeywell UCN (Universal Control Network) network. As an interface unit between APM/HPM controllers and field instruments, it is responsible for collecting, conditioning, isolating 4-20mA standard analog signals and transmitting them to the control system. It is widely used in signal acquisition in the process control fields such as petroleum, chemical, and power.
II. Core Specification Parameters
Number of channels: 32 channels (32 independent analog input channels)
Input signal: Standard 4-20mA DC (two-wire / three-wire transmitter compatible)
Signal isolation: Electrical isolation between channels (group isolation), anti-common-mode interference
Connection method: Industrial-grade screw terminals, supports direct connection of field cables
Built-in functions: Signal filtering, surge protection, overvoltage suppression, loop verification
Compatible controllers: APM (Advanced Process Manager), HPM (High Performance Process Manager)
Physical characteristics: Standard DCS rail mounting, flame-retardant material (UL 94V-0)
Operating environment:
Temperature: -20°C ~ +70°C
Humidity: 5% ~ 95% RH (no condensation)
Electrical parameters:
Power supply: 24V DC (system-side power supply)
Power consumption: ≤ 100mA @ 24V DC
Isolation voltage: ≥ 500V AC
Certification: CE, UL certification
Warranty: Original factory 12-month warranty
III. Main Functional Characteristics
High-density signal access: 32 channels of 4-20mA signals centralized access, significantly saving cabinet space
Signal conditioning protection: Built-in filtering, surge suppression, overcurrent protection, improving signal stability
Electrical isolation: Channel group isolation design, blocking interference from the field from entering the system, protecting the controller
Transformer compatibility: Supports two-wire and three-wire 4-20mA transmitters (pressure, temperature, flow, level)
Convenient maintenance: Supports hot swapping, single-channel failure does not affect other channels, online calibration
Reliable connection: Tight connection with screw terminals, suitable for complex industrial environments
IV. System Adaptation and Model Interchange
Applicable systems: TDC 3000, TPS, Experion PKS
Matching cards: UCN analog input (AI) main card (e.g. 51204155-xxx)
Replacement / Interchange models:
51204160-125 (MU-TAIY62): Functionally identical, earlier version, can be directly interchanged
Related models of the same series:
51204156-175 (MC-TDOY62): 32-channel DO FTA
51204168-150 (MC-TAIH62): High-level analog input FTA
V. Installation and Application Tips
Standard DCS cabinet rail installation, supports vertical / horizontal installation
Analog signal lines use shielded twisted-pair cables, laid separately away from power cables
Single-ended reliable grounding of the shield layer to avoid circulating interference
Strictly distinguish positive and negative signals and common terminal wiring
Application scenarios:
Pressure transmitter signal acquisition
Temperature transmitter (4-20mA) signal connection
Flow, level instrument signal input
Valve positioner feedback signal acquisition
VI. Order Information
Order model: 51204160175 (51204160-175)
Product name: MC-TAIY62 32-channel 4-20mA analog input FTA
Product status: Mainly in use model, market stock is sufficient
Replacement model: 51204160-125 (MU-TAIY62)
Get a Quote