Description
CUTLER-HAMMER HMCPS003A0C Magnetic Motor Circuit Protector Description
Overview
CUTLER-HAMMER HMCPS003A0C is a Series C magnetic-only motor circuit protector (MCP), belonging to Eaton Cutler-Hammer HMCP family. This motor circuit protector provides instantaneous short-circuit protection for three-phase motor branch circuits, and the motor circuit protector must pair with a separate overload relay to achieve complete motor overload protection. The motor circuit protector is widely matched with contactors to build NEMA motor starters for North American control panels.
Features
CUTLER-HAMMER HMCPS003A0C adopts magnetic instantaneous trip design without thermal overload element, the adjustable magnetic trip range is 9–30A for the 3A frame variant. This motor circuit protector supports optional auxiliary contact blocks to feedback trip status to PLC and alarm systems. It has molded case housing and high short-circuit breaking capacity, complying with UL489 standard. This motor circuit protector supports Type 1 coordination to reduce arc damage to contactor contacts during short-circuit fault. The suffix C stands for copper terminals variant, and it carries UL, CSA and CE certifications for industrial cabinet applications.
Technical Parameters
CUTLER-HAMMER HMCPS003A0C belongs to Series C HMCP motor circuit protector family. Rated continuous current is 3A, magnetic trip setting range 9–30A. Rated voltage 600VAC / 250VDC. It is a 3-pole device, standard screw terminal connection. It only provides short-circuit protection; overload protection needs independent thermal overload relay. DIN rail mounting, enclosure protection grade IP20.
Working Principle
CUTLER-HAMMER HMCPS003A0C continuously monitors the current of the motor branch circuit. When short-circuit fault occurs, huge fault current generates strong magnetic force inside to trip the main contacts instantly. Normal overload current will not trigger this MCP, overload protection is handled by the matched overload relay. After tripping, manual reset is required once the fault is cleared. Optional auxiliary contacts change state synchronously to transmit fault signals to the control system for interlock and alarm action.
Application Fields
CUTLER-HAMMER HMCPS003A0C is widely used for small pumps, fans, conveyors and automated machinery in North American style motor starter control panels. It serves as short-circuit protection branch unit for three-phase motor loads. This motor circuit protector is a common replacement spare part for maintaining Eaton Cutler-Hammer legacy motor control systems.